Laars heating systems – LAARS 9600 CB - Installation, Operation and Maintenance Instructions User Manual
Page 6
![background image](/manuals/697796/6/background.png)
Page 6
LAARS Heating Systems
U.S. Installations (see note 1)
Canadian Installations (see note 2)
A=
Clearance above grade, veranda, porch,
12 inches (30 cm)
12 inches (30 cm)
deck, or balcony
B=
Clearance to window or door that may
12 inches (30 cm)
36 inches (91 cm)
be opened
C=
Clearance to permanently closed window
See note 4
See note 5
D=
Vertical clearance to ventilated soffit located
above the terminal within a horizontal
See note 4
See note 5
distance of 2 feet (61cm) from the
center line of the terminal
E=
Clearance to unventilated soffit
See note 4
See note 5
F=
Clearance to outside corner
See note 4
See note 5
G=
Clearance to inside corner
See note 4
See note 5
H=
Clearance to each side of center line
See note 4
3 feet (91 cm) within a height 15 feet above
extended above meter/regulator assembly
the meter/regulator assembly
I=
Clearance to service regulator vent outlet
See note 4
3 feet (91 cm)
J=
Clearance to nonmechanical air supply inlet
12 inches (30 cm)
36 inches (91 cm)
to building or the combustion air inlet to
any other appliance
K=
Clearance to a mechanical air supply inlet
3 feet (91 cm) above if within 10 feet (3 m)
6 feet (1.83 m)
horizontally
L=
Clearance above paved sidewalk or paved
Vent termination not allowed in this location
Vent termination not allowed in this location
driveway located on public property
for category IV appliances.
for Category IV appliances.
M= Clearance under veranda, porch, deck,
See note 4
12 inches (30 cm) (see note 3)
or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CGA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of
the gas supplier.
5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas
supplier.
Figure 5A. Vent terminal clearances.