LAARS EBP 175 MBTU/h - Installation, Operation and Maintenance Instructions User Manual
Page 33

Endurance
Page 33
fault indicates that there is either something
mis-wired on the boiler, or that the relay
in this circuit has seized. Check the relay
for seized contacts first, and if the relay is
operational, check the wiring circuit on the
boiler.
F-4 Check for damaged wiring or poor
connection at sensor plug. If they are OK
disconnect the sensor plug and check the
resistance across the sensor terminals. The
resistance of a good sensor is 1035 ohms @
77°F (25°C). Replace sensor if resistance is
less than 500 or more than 20,000 ohms.
F-5 Correct in the same manner as F-4.
F-6 Correct in the same manner as F-4.
F-8 Check that the outdoor air sensor is
installed properly, and that the wire and/
or connection are not damaged. If okay,
disconnect the sensor and check the
resistance across the sensor terminals. The
resistance of a good sensor is 1035 ohms at
77°F (25°C). Replace sensor is resistance is
less than 500 or more than 20,000 ohms.
LO See
Section 9.2.3
OFF Control power is off. Press and hold the
power button (upper left button) on the
boiler control for 3 seconds to restore
control power. The control will flash “ON”
and then will return to normal operation.
9.2.3 Resolving Lockouts (LO)
There are many causes for lockouts. The six most
common causes are: (a) poor combustion,
(b) poor flame sensor signal, (c) inadequate gas supply,
(d) ignitor failure, (e) blocked or contaminated air
source, (f) safety limit trip. If you get LO on boiler
control, you need to check the ignition control to see if
it is flashing three times, for ignition control lockout. If
it is, then that is a combustion lockout.
a. Poor Combustion: Poor combustion should be
suspected if there is a strong flue gas odor. The
odor may result from either an improper gas/
air ration (high or low CO
2
) or contamination
of the combustion air supply. If an improper
gas/air ratio is suspected refer to “gas valve
calibration (offset adjustment)” in
Section 10
.
If contamination of the air source is suspected,
check the vent system for leaks back into the
combustion air.
b. Poor flame sensor signal: The boiler control
board will lockout if the flame sensor is grounded
or if the flame signal it receives is less than 1
μA
dc. To check for a grounded sensor, remove
the flame sensor wire (yellow) from the boiler
control board and check for continuity between
the yellow wire terminal and the combustion
chamber bottom pan. If there is continuity, the
flame sensor is grounded. An alternate way to
check for grounding of the flame sensor is to
check the ohms resistance between the yellow
wire terminal and the combustion chamber
bottom pan, using a meter set for at least 100,000
ohms. The resistance must be more than 250,000
ohms (some technicians have been confused
by meters which report infinite resistance with
what appears to them as double zeros; an infinite
resistance reading means there is no grounding
of the flame sensor.) If there is continuity, or
the ohms resistance is less than 250,000 ohms,
debris or moisture in the combustion chamber
may be the cause. To correct, carefully remove
the ignitor and flame sensor assembly. Look
for debris on the assembly where the flame rod
exits the ceramic tube. If debris exists, remove
it. If this area is clean, insert a pencil or other
round object into the flame sensor hole in the
bottom combustion chamber pan and roll it
around to clear any debris that may exist inside
the combustion chamber. Replace the ignitor/
flame sensor assembly, reconnect the yellow wire
and start the boiler. If lockout persists, check
the flame signal. The minimum flame current
necessary to keep the system from lockout is 1
microamp (
μA). There is no need to disconnect
anything to measure the flame current signal.
To measure the flame signal, connect an analog
DC microammeter to the FC terminals on the
ignition control, per Figure 37. The meter should
read 1
μA or higher. (If the meter reads below
“0” on the scale, the meter leads are reversed.
Disconnect and reconnect the meter for correct
polarity.) If the meter reading is less than 1
μA,
see the “poor combustion” section. (Check for air
leaks at inlet to blower.)
c. Inadequate gas supply: Before proceeding,
ensure that the gas supply has not been shutoff
or the LP tank (LP boilers) is not empty. Then,
reset the boiler and observe the operational cycle.
Approximately 20 seconds after the start of the
cycle, the GV LED on the boiler control should
light. If it does not, reset the boiler and check
for 24 VAC at the boiler control. If the voltage
is less than 20 VAC, and transformer voltage is
24 VAC replace the boiler control. If the voltage
is correct, connect a pressure gauge to the offset
pressure port on the gas valve. Reset the boiler
and observe the offset pressure at startup and
after 20 seconds. The pressure will be ~ -2 in.
w.c. at startup (during prepurge) and should
become less negative (-0.1 in. w.c.) when the gas
valve opens and gas flow starts. If the pressure
remains at ~ -2 in. w.c. throughout the cycle
replace the gas valve.