beautypg.com

Warning, Caution – Carrier 50CR User Manual

Page 11

background image

11

Duct Covers

A05301

Fig. 11 -- 50CR with Duct Covers On

1” (25mm) MIN.

2” (50mm) MIN.

TRAP
OUTLET

C99013

Fig. 12 -- Condensate Trap

Step 7—Install Electrical Connections

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury

or death.
The unit cabinet must have an uninterrupted, unbroken

electrical ground to minimize the possibility of personal injury

if an electrical fault should occur. This ground may consist of

an electrical wire connected to the unit ground screw in the

control compartment, or conduit approved for electrical

ground when installed in accordance with NEC, ANSI/NFPA

American National Standards Institute/National Fire

Protection Association (latest edition) (in Canada, Canadian

Electrical Code CSA C22.1) and local electrical codes.

!

WARNING

HIGH--VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a

field--supplied, waterproof disconnect switch mounted at, or within
sight from the unit. Refer to the unit rating plate, NEC and local

codes for maximum fuse/circuit breaker size and minimum circuit

amps (ampacity) for wire sizing (See Table 2 for electrical data).
The field--supplied disconnect may be mounted on the unit over the

high--voltage inlet hole (See Fig. 6 and 7).
If the unit has an electric heater, a second disconnect may be

required. Consult the Installation, Start--Up, and Service
Instructions provided with the accessory for electrical service

connections.
Operation of unit on improper line voltage constitutes abuse and
may cause unit damage that could affect warranty.

UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit

being installed.

1. Make all electrical connections in accordance with NEC

ANSI/NFPA (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical

connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable local
codes. Refer to unit wiring diagram.

2. Use only copper conductor for connections between

field--supplied electrical disconnect switch and unit. DO

NOT USE ALUMINUM WIRE.

3. Be sure that high--voltage power to unit is within operating

voltage range indicated on unit rating plate. On 3--phase

units, ensure phases are balanced within 2 percent. Consult
local power company for correction of improper voltage

and/or phase imbalance.

4. Insulate low--voltage wires for highest voltage contained

within conduit when low--voltage control wires are in same
conduit as high--voltage wires.

5. Do not damage internal components when drilling through

any panel to mount electrical hardware, conduit, etc.

!

CAUTION

ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The high
voltage leads should be in a conduit until they enter the duct panel;

conduit termination at the duct panel must be watertight. Run the
high--voltage leads through the power entry knockout on the power

entry side panel. See Fig. 6 and 7 for location and size. For

single--phase units, connect leads to the black and yellow wires ; for
3--phase units, connect the leads to the black, yellow, and blue wires.
CONNECTING GROUND LEAD TO GROUND SCREW
Connect the ground lead to the chassis using the ground screw in the

wiring splice box (See Fig. 14 and 17).
ROUTING CONTROL POWER WIRES
For detailed instruction on the low voltage connections to the User

Interface (UI), refer to the UI installation guide.
Form a drip--loop with the control leads before routing them into the

unit. Route the low voltage control leads through grommeted,
low--voltage hole provided into unit (See Fig. 6 and 7). Connect user

interface leads to unit control power leads as shown in Fig. 14.
The unit transformer supplies 24--v power for complete system
including accessory electrical heater. A fuse is provided in the 24--v

circuit on the control board (See Fig. 19); see the caution label on
the transformer. Transformer is factory wired for 230--v operation.

If supply voltage is 208--v, rewire transformer primary as described

in Special Procedures for 208--v Operation section.

50C

R