Table 1—Physical Data -- Unit 50CR

UNIT SIZE

024

030

036

042

048

060

NOMINAL CAPACITY (ton)

2

2--1/2

3

3--1/2

4

5

OPERATING WEIGHT (lb.)

350

350

373

440

463

499

Compressor

Scroll

Refrigerant (R--410A) Quantity (lb.)

7.5

8

9.5

10.8

11.5

14.0

REFRIGERANT METERING DEVICE

TXV

ORIFICE OD (in.)

0.035 (2)

0.035 (2)

0.038 (2)

0.038 (2)

0.038 (Left OD Coil)

0.046 (Right OD Coil)

0.042 (Left OD Coil)

0.052 (Right OD Coil)

OUTDOOR COIL

RowsFins/in.

2…21

2…21

2…21

2…21

2…21

2…21

Face Area (sq. ft.)

12.3

12.3

13.6

15.4

17.2

19.4

OUTDOOR FAN

Nominal Cfm

2700

2700

2800

2800

3300

3300

Diameter

22

22

22

22

22

22

Motor HP (RPM)

1/8 (825)

1/8 (825)

1/8 (825)

1/8 (825)

1/4 (1100)

1/4 (1100)

INDOOR COIL

RowsFins/in.

3…15

3…15

4…15

3…15

4…15

4…17

Face Area (sq. ft.)

3.7

3.7

3.7

4.7

4.7

5.7

INDOOR BLOWER

Nominal Airflow (Cfm)

Comfort

Variable based on Comfort Roll back (see User Interface instructions for more information).

Efficiency

700

875

1050

1225

1400

1750

Max

800

1000

1200

1400

1600

2000

Size (in.)

10x10

10x10

11x10

11x10

11x10

11x10

Motor HP (RPM)

1/2

1/2

3/4

3/4

3/4

1

HIGH--PRESSURE SWITCH (psig)

650 ± 15

420 ± 25

Cutout

Reset (Auto)

LOSS--OF--CHARGE/LOW--PRESSURE SWITCH

20 ± 5

45 ± 10

(Liquid Line) (psig)

Cutout

Reset (Auto)

Return--Air Filters (in.)*

20x24x1

20x24x1

24x30x1

24x36x1

24x36x1

24x36x1

Throwaway

*Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute
for throwaway type or 450 ft/minute for high--capacity type. Air filter pressure drop for non--standard filters must not exceed 0.08 in. wg.

USER
INTERFACE

DISCONNECT
PER NEC*

FROM
POWER
SOURCE

RETURN
AIR

TOP COVER

FROM
GAS LINE

*NEC - NATIONAL ELECTRICAL CODE

A06091

Fig. 10 -- Typical Installation

50C

R