Power Supply —

Electrical characteristics of available

power supply must agree with unit nameplate rating. Supply
voltage must be within limits shown in Table 3.

IMPORTANT: Operating unit on improper supply volt-
age, or with excessive phase imbalance, constitutes abuse
and may affect Carrier warranty. See Unbalanced 3-Phase
Supply Voltage, page 7.

Power Wiring —

All power wiring must comply with

applicable local and national codes. Install field-supplied branch
circuit fused disconnect(s) per NEC (National Electrical Code,
U.S.A.) of a type that can be locked OFF or OPEN. Dis-
connect(s) must be within sight from and readily accessible
from unit in compliance with NEC Article 440-14.

GENERAL WIRING NOTES
1. A crankcase heater is wired in the control circuit so it is

always operable as long as power supply disconnect is
on, even if any safety device is open or unit stop-start
switch is off. It is protected by a 5-amp circuit breaker in
control power.

2. The power circuit field supply disconnect should never be

open except when unit is being serviced or is to be down
for a prolonged period. When operation is resumed, crank-
case heater should be energized for 24 hours before start-
up. If unit is to be shut down for a prolonged period, it
is recommended that the suction and discharge valves be

closed to prevent an excessive accumulation of refriger-
ant in the compressor oil.

3. Power entry is one end only.
4. Maximum field wire sizes allowed by lugs on terminal

block are:

UNIT

38AKS

V-Ph-Hz

WIRE
SIZE*

028

208/230-3-60

350 kcmil

034

208/230-3-60

230-3-50

044

208/230-3-60

230-3-50

LEGEND

AWG — American Wire Gage
kcmil — Thousand Circular Mils
*All other units use 2/0 AWG (67.4 mm

2

).

5. Terminals for field power supply are suitable for copper,

copper-clad aluminum, or aluminum conductors. Insula-
tion must be rated 167 F (75 C) minimum.

CONDENSER FANS — The fans must rotate counterclock-
wise when viewed from above. If necessary, correct direc-
tion of fan rotation by interchanging any 2 power input wires
at disconnect switch. Affix crankcase heater decal (located
in installer’s packet) to unit disconnect switch.

Table 3 — Electrical Data

60 HZ

UNIT

38AKS

UNIT

COMPRESSOR

FAN MOTORS

Volts

3 Ph, 60 Hz

Supplied*

MCA

MOCP
(Fuse)

ICF

RLA

LRA

FLA (ea)

Qty

Min.

Max.

028

500
200
600
100

208/230

380
460
575

187
342
414
518

254
418
508
632

124.6

64.7
60.7
52.5

200

110

100

80

452.2
250.9
226.1
167.4

89.8
45.5
43.6
36.5

446
247
223
164

6.2
3.9
3.1
3.4

2
2
2
2

034

500
200
600
100

208/230

380
460
575

187
342
414
518

254
418
508
632

145.5

72.5
68.7
54.9

250
125

110

90

512.2
283.9
256.1
179.4

106.5

52.6
50.0
38.5

506
280
253
176

6.2
3.9
3.1
3.4

2
2
2
2

044

500
200
600
100

230
380
460
575

187
342
414
518

254
418
508
632

203.0

111.1

91.0
81.5

350
175
150
125

702.4
389.8
351.2
282.8

147.5

79.5
65.4
57.1

690
382
345
276

6.2
3.9
3.1
3.4

3
3
3
3

50 HZ

UNIT

38AKS

UNIT

COMPRESSOR

FAN MOTORS

Volts

3 Ph, 50 Hz

Supplied*

MCA

MOCP
(Fuse)

ICF

RLA

LRA

FLA (ea)

Qty

Min.

Max.

028

800
300
900

230
346
400

198

311

342

254
380
400

109.0

64.9
60.5

175
100
100

348.4
263.4
226.0

76.9
44.9
43.6

342
259
223

6.4
4.4
3.0

2
2
2

034

800
300
900

230
346
400

198

311

342

254
380
400

120.2

76.1
68.5

200
125

110

372.4
298.4
256.0

85.9
53.9
50.0

366
294
253

6.4
4.4
3.0

2
2
2

044

800
300
900

230
346
400

198

311

342

254
380
400

150.6

112.6

90.8

250
175
150

557.8
408.8
351.0

105.1

79.5
65.4

545
400
345

6.4
4.4
3.0

3
3
3

LEGEND

CSA

Canadian Standards Association

FLA

Full Load Amps

ICF

Maximum Instantaneous Current Flow during starting (the point

in the starting sequence where the sum of the LRA for the start-
ing compressor, plus the total FLA for all running fan motors is
maximum).

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (complies with National

Electrical Code [NEC, U.S.A.], Section 430-24)

MOCP — Maximum Overcurrent Protection
RLA

Rated Load Amps

UL

Underwriters’ Laboratories

*Units are suitable for use on electrical systems where voltage sup-

plied to unit terminals is not below or above listed minimum and maxi-
mum limits.

6