beautypg.com

Compaq ALPHA GS320 User Manual

Page 28

background image

28

8.11 Operating Environment

Temperature range:

21oC +3oC (70oF+5oF)

Temperature rate of change:

Maximum of 3oC/hour (5.4oF/hour)

Temperature adjustment for altitude:

Reduce the operating temperature by

1.8oC/1000 meters (1oF/1000

feet)
Relative humidity range:

50% RH+10% (no condensation)

Relative humidity rate of change:

Maximum of 6%/hour

8.12 Shipping And Storage In Shipment Containers For Less Than 60 Days

Temperature range:

-40o to 66oC (-40o to 151oF)

Temperature rate of change:

Maximum of 20oC/hour (36oF/hour)

Relative humidity range:

0 to 95% RH (no condensation)

8.13 Storage In Shipment Containers For More Than 60 Days

Temperature range:

5o to 50oC (40o to 122oF)

Temperature rate of change:

Maximum of 11oC/hour (20oF/hour)

Relative humidity range:

10 to 95% RH (no condensation)

Wet bulb temperature:

Maximum of 32oC (90oF)

8.14 Altitude

Most equipment has been normally tested on a short-term basis for performance, up to an altitude of 2.4 kilometers
(8000 feet). Above this altitude, the operation of equipment may be impaired.

8.15 Airflow Rate Range

266-314 m3/h-kilowatts or 550-650 cfm/ton at the air-conditioner output

8.16 Vibration

Most equipment has been normally tested on a short-term basis for performance up to the vibration limits specified
below. Above these limits or with a continuous vibration level, the operation of equipment may be impaired

Frequency (Hertz)

Amplitude

5 - 22

0.254 millimeters (0.010 inches) double amplitude

22-500

0.25 g peak