LDU 68.1 & 68.2 Technical Manual, Rev. 12 January 2010

Page 22 of 28

8.9. Setpoint Output Commands – Sn, Hn, An

The LDU 68.1 has 2 logic outputs where the status depends on the weight value (setpoint). Each logic output
can be assigned an independent setpoint value (Sn) with a corresponding hysteresis/switch action (Hn) and
allocation (An – switch on the gross or the net weight).

8.9.1. S0 / S1

Setpoint Value

Master (PC / SPS) sends

Slave (LDU XX.X) responds

Meaning

S0

O+01500

Request: Setpoint S0 = 1500 d

S0 03000

OK

Setup: Setpoint S0 = 3000 d

S1

O+01500

Request: Setpoint S1 = 1500 d

S1 03000

OK

Setup: Setpoint S1 = 3000 d

8.9.2. H0 / H1

Setpoint Hysteresis and Switching Action

The wished switching logic will be defined by the numeric value and the polarity of the setpoint hysteresis.
The outputs can operate as “normally closed” (negative polarity) or “normally open” (positive polarity).

Example

Setpoint

Hysteresis

Weight

Output open

Output closed

S0 = 2000 kg

H0 = -100kg

increasing

> 2100 kg

 2100 kg

S0 = 2000 kg

H0 = -100kg

decreasing

2000 kg

< 2000 kg

S0 = 2000 kg

H0 = 100kg

increasing

 2000 kg

> 2000 kg

S0 = 2000 kg

H0 = 100kg

decreasing

< 1900 kg

1900 kg

Example for negative hysteresis and setpoint S0 = 2000 kg (line 1 + 2 of the table above):
When the weight is increasing between 0 kg and 2100 kg the logic output is “closed”. Once the weight exceeds
2100 kg then the logic output will be “open”. The logic output will get “closed” again when the weight value
drops below 2000 kg.

Example for positive hysteresis and setpoint S0 = 2000 kg (line 3 + 4 of the table above):
When the weight is increasing between 0 kg and 2000 kg the logic output is “open”. Once the weight exceeds
2000 kg then the logic output will be “closed”. The logic output will re-open again when the weight value drops
below 1900 kg.

Master (PC / SPS) sends

Slave (LDU XX.X) responds

Meaning

H0

O-00100

Request: neg. hysteresis setpoint S0

H0 100

OK

Setup: pos. hysteresis setpoint S0

H1

O-00100

Request: neg. hysteresis setpoint S1

H1 100

OK

Setup: pos. hysteresis setpoint S1

Allowed hysteresis values are within the range from –99999 to +99999 at a step size of 1.

8.9.3. A0 / A1

Allocation of Gros or Net Value

Allowed allocation

Meaning

A0 = 0

Gros value controls setpoint S0

A0 = 1

Net value controls setpoint S0

A1 = 0

Gros value controls setpoint S1

A1 = 1

Net value controls setpoint S1


Master (PC / SPS) sends

Slave (LDU XX.X) responds

Meaning

A0

O+00000

Request: Gros for setpoint S0

A0 1

OK

Setup: Net for setpoint S0

A1

O-00000

Request: Gros for setpoint S1

A1 1

OK

Setup: Net for setpoint S1

Note:

All changes to the setpoint settings have to be stored in the EEPROM using the SS command. See

chapter 8.11