Table 7 — Electrical Data, 074 Units

208/230-3-60 (V-Ph-Hz)

VOLTAGE

RANGE

COMPR

NO. 1

COMPR

NO. 2

OFM

IFM

BASE UNIT

ONLY

EXHAUST

FAN

ELECTRIC

HEAT*

BASE UNIT WITH

EXHAUST FAN

AND/OR

ELECTRIC HEAT*

RLA

LRA

RLA

LRA

Total

FLA

Hp

FLA

MCA

MOCP

Total

Hp

Total

FLA

kW

FLA

MCA

MOCP

187-254

107.7

506.0

142.3

690.0

27.8

15.0

46.2/
42.0

358.8/
854.6

500/
450

10.0

33.4/30.4

392.2/385.0

500/500

15.0

48.4/44.0

407.2/398.6

500/500

20.0

61.6/56.0

420.4/410.6

500/500

29/ 36

78.9/ 91.0

358.8/354.6

500/450

59/ 72

157.7/182.0

358.8/354.6

500/450

88/108† 236.6/273.0

358.8/393.8

500/450

10.0

33.4/30.4

29/ 36

78.9/ 91.0

392.2/385.0

500/500

10.0

33.4/30.4

59/ 72

157.7/182.0

392.2/385.0

500/500

10.0

33.4/30.4

88/108† 236.6/273.0

392.2/393.8

500/500

15.0

48.4/44.0

29/ 36

78.9/ 91.0

407.2/398.6

500/500

15.0

48.4/44.0

59/ 72

157.7/182.0

407.2/398.6

500/500

15.0

48.4/44.0

88/108† 236.6/273.0

407.2/398.6

500/500

20.0

61.6/56.0

29/ 36

78.9/ 91.0

420.4/410.6

500/500

20.0

61.6/56.0

59/ 72

157.7/182.0

420.4/410.6

500/500

20.0

61.6/56.0

88/108† 236.6/273.0

420.4/410.6

500/500

20.0

59.4/
64.0

372.0/
366.6

500/
500

10.0

33.4/30.4

405.4/397.0

500/500

15.0

48.4/44.0

420.4/410.6

500/500

20.0

61.6/56.0

433.6/422.6

500/500

29/ 36

78.9/ 91.0

372.0/366.6

500/500

59/ 72

157.7/182.0

372.0/366.6

500/500

88/108† 236.6/273.0

372.0/408.8

500/500

10.0

33.4/30.4

29/ 36

78.9/ 91.0

405.4/397.0

500/500

10.0

33.4/30.4

59/ 72

157.7/182.0

405.4/397.0

500/500

10.0

33.4/30.4

88/108† 236.6/273.0

405.4/408.8

500/500

15.0

48.4/44.0

29/ 36

78.9/ 91.0

420.4/410.6

500/500

15.0

48.4/44.0

59/ 72

157.7/182.0

420.4/410.6

500/500

15.0

48.4/44.0

88/108† 236.6/273.0

420.4/410.6

500/500

20.0

61.6/56.0

29/ 36

78.9/ 91.0

433.6/422.6

500/500

20.0

61.6/56.0

59/ 72

157.7/182.0

433.6/422.6

500/500

20.0

61.6/56.0

88/108† 236.6/273.0

433.6/422.6

500/500

25.0

74.8/
68.0

387.4/
380.6

500/
500

10.0

33.4/30.4

420.8/411.0

500/500

15.0

48.4/44.0

435.8/424.6

500/500

20.0

61.6/56.0

449.0/436.6

500/500

29/ 36

78.9/ 91.0

387.4/380.6

500/500

59/ 72

157.7/182.0

387.4/380.6

500/500

88/108† 236.6/273.0

389.3/426.3

500/500

10.0

33.4/30.4

29/ 36

78.9/ 91.0

420.8/411.0

500/500

10.0

33.4/30.4

59/ 72

157.7/182.0

420.8/411.0

500/500

10.0

33.4/30.4

88/108† 236.6/273.0

420.8/426.3

500/500

15.0

48.4/44.0

29/ 36

78.9/ 91.0

435.8/424.6

500/500

15.0

48.4/44.0

59/ 72

157.7/182.0

435.8/424.6

500/500

15.0

48.4/44.0

88/108† 236.6/273.0

435.8/426.3

500/500

20.0

61.6/56.0

29/ 36

78.9/ 91.0

449.0/436.6

500/500

20.0

61.6/56.0

59/ 72

157.7/182.0

449.0/436.6

500/500

20.0

61.6/56.0

88/108† 236.6/273.0

449.0/436.6

500/500

30.0

88.0/
80.0

400.6/
392.6

500/
500

10.0

33.4/30.4

434.0/423.0

500/500

15.0

48.4/44.0

449.0/436.6

500/500

20.0

61.6/56.0

462.2/448.6

600/500

29/ 36

78.9/ 91.0

400.6/392.6

500/500

59/ 72

157.7/182.0

400.6/392.6

500/500

88/108† 236.6/273.0

405.7/441.3

500/500

10.0

33.4/30.4

29/ 36

78.9/ 91.0

434.0/423.0

500/500

10.0

33.4/30.4

59/ 72

157.7/182.0

434.0/423.0

500/500

10.0

33.4/30.4

88/108† 236.6/273.0

434.0/441.3

500/500

15.0

48.4/44.0

29/ 36

78.9/ 91.0

449.0/436.6

500/500

15.0

48.4/44.0

59/ 72

157.7/182.0

449.0/436.6

500/500

15.0

48.4/44.0

88/108† 236.6/273.0

449.0/441.3

500/500

20.0

61.6/56.0

29/ 36

78.9/ 91.0

462.2/448.6

600/500

20.0

61.6/56.0

59/ 72

157.7/182.0

462.2/448.6

600/500

20.0

61.6/66.0

88/108† 236.6/273.0

462.2/448.6

600/500

LEGEND

CV

Constant Volume

ETL

ETL Testing Laboratory

FLA

Full Load Amps

Hp

Nominal Horsepower

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

MOCP — Maximum Overcurrent Protection
OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Electric heat available on 50 Series vertical discharge units.

†108 kW available on CV applications only.

NOTES:
1. Electric resistance heaters are rated at 208/240 v, 480 v, or 575 v. To

determine heater capacity (kW) at unit operating voltage, multiply 240 v,
480 v, or 575 v capacity by appropriate multiplier below.

MULTIPLICATION FACTORS

HEATER kW

RATING

VOLTAGE

DISTRIBUTION

V-3-60

MULTIPLICATION

FACTOR

240

200
208
230
240

0.694
0.751
0.918
1.000

480

440
460
480

0.840
0.918
1.000

575

550
575
600

0.915
1.000
1.089

Electric heaters are tested and ETL approved at maximum
total external static pressure of 1.9 in. wg.

2. Boldface indicates 48 and 50 Series units. All other data is for 50 Series