beautypg.com

Service, Warning – Carrier 50HE003-006 User Manual

Page 62

background image

62

C06137

Fig. 53

--- Humidi--Mizert Hot Gas

Reheat Mode Operation

Hot Gas Reheat Mode
When the humidity levels in the space require humidity control, a

hot gas solenoid valve (specific to hot gas reheat mode only) will
open to bypass a portion of hot gas refrigerant around the

condenser coil. (See Fig. 53.)
This hot gas will mix with liquid refrigerant leaving the

condenser

coil

and

flow

to

the

subcooling/reheat

dehumidification coil. Now the conditioned air coming off the
evaporator will be cooled and dehumidified, but will be warmed

to neutral conditions (72_F to 75_F) by the subcooling/reheat
dehumidification coil.
The net effect of the rooftop when in hot gas reheat mode is to

provide nearly all latent capacity removal from the space when
sensible loads diminish (when outdoor temperature conditions are

moderate). When in hot gas reheat mode, the unit will operate to
provide mostly latent capacity and extremely low sensible heat

ratio capability.
Similar to the subcooling mode of operation, hot gas reheat mode
operates only when the outside air temperature is warmer than

40_F. Below this temperature, a factory installed outside air
temperature switch will lockout this mode of operation.
See Table 36 for the Humidi-Mizer adaptive dehumidification
system sequence of operation.

SERVICE

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal

injury or death.
When sevicing unit, shut off all electrical power to unit

and install lockout tag.

!

WARNING

Step 1

—Cleaning

Inspect unit interior at the beginning of heating and cooling

season and as operating conditions require.
Evaporator Coil

1. Turn unit power off, tag disconnect. Remove evaporator

coil access panel.

2. If economizer or two-position damper is installed, remove

economizer

by

disconnecting

Molex

plug

and

removing mounting screws.

3. Slide filters out of unit.

4. Clean coil using a commercial coil cleaner or dishwasher

detergent in a pressurized spray canister. Wash both sides

of coil and flush with clean water. For best results,
back-flush toward return-air section to remove foreign
material. Flush condensate pan after completion.

5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.

Condenser Coil
Inspect coil monthly. Clean condenser coil annually, and as

required by location and outdoor air conditions.
One--Row Coil
Wash coil with commercial coil cleaner. It is not necessary to
remove top panel.
2-Row Coils
Clean coil as follows:

1. Turn off unit power and tag disconnect.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. (See Fig. 54.) To hold

top panel open, place coil corner post between top panel

and center post. (See Fig. 55.)

C06044

Fig. 54

--- Cleaning Condenser Coil

C06045

Fig. 55

--- Propping Up Top Panel

50H

E,

H

J

This manual is related to the following products: