12. Using the accessory-supplied M6 screws (3000A or

3100A: Item 6), install the accessory-supplied junction

box (3000A or 3100A: Item 5) at the desired location

where the entering and leaving water thermistor cables

can be conveniently spliced. One or two knockouts can

be used. Follow all local codes. Remove one knockout

from the junction box and install the field-supplied strain

relief at the knockout hole. If using field-supplied conduit

to provide mechanical protection to the thermistor wires

between the cooler and the 30XA base unit, remove

another knockout.

13. To reconnect the thermistors, locate the entering water

thermistor and leaving water thermistor and cut both

leads where they can be spliced in the installed junction

box. Cut, strip, and label both sides of the entering water

thermistor lead “EWT.” Cut, strip, and label the leaving

water thermistor lead the same way, with “LWT” on both

sides. See Fig. 13.

14. Run the labeled thermistor leads connected to the unit

into the installed junction box and tighten the field-

supplied strain relief. Strip back the lead jackets to expose

the two wires in each lead.

15. Take one of the accessory-supplied 5-wire jacketed ca-

bles (3000A or 3100A: Item 3) to connect the thermistor

leads in the installed junction box to the cooler location.

Each wire in the jacketed cable is a different color. Cut

the cable into two pieces so that each has a maximum

length of 100 ft (30.5 m).

16. Select one jacketed cable and strip back the jacket on

both ends to expose the five wires. Pick any two wires

and label both ends of each wire “EWT.” Pick another

pair of wires and label both ends “LWT.” The fifth wire is

not used. See Fig. 14.

17. Run one end of the accessory-supplied 5-wire jacketed

cable into the installed junction box and splice the identi-

cally labeled thermistor leads. Solder the splices and insu-

late them to prevent shorting. Tighten the field-supplied

strain relief for the cables.

18. Run the other end of the accessory-supplied 5-wire

jacketed cables back to the cooler. Splice the labeled

jacketed cable wires to the matching thermistors. If a

second junction box is necessary at the cooler location,

use the second accessory-supplied junction box (3000A

or 3100A: Item 5).

19. Reinstall the thermistors in the correct cooler wells.

20. To reconnect the suction pressure transducers (SPT),

locate the SPT plugs for circuits A and B, and cut the

leads where they can be conveniently spliced in the

installed junction box at the 30XA base unit. Label the

leads “SPTA” for the circuit A lead, and “SPTB” for the

circuit B lead.

21. Take the two pieces of accessory-supplied transducer

wire harness (3000A: Item 16 or 3100A: Item 14). One

side of the harness is a plug and the other side is three

wires in red, black, and green. Label both sides of one

harness “SPTA,” and label the other harness “SPTB.”

Remove one knockout from an installed junction box and

install a field-supplied strain relief valve at the knockout

hole. If using field-supplied conduit to provide mechani-

cal protection to the transducer wires between the cooler

and the 30XA base unit, remove another knockout.

22. Run the labeled transducer leads connected to the unit

into the installed junction box at the 30XA base unit and

tighten the field-supplied strain relief. Strip back the lead

jackets to expose the three wires, black, red, and white.

23. Run the lead end of accessory-supplied transducer wire

harnesses into the junction box and splice the identically

labeled leads. The red wire should go with red wire, the

black wire with the black wire, and the white wire with

the green wire. Solder the splices and insulate them to

prevent shorting. Tighten the field-supplied strain relief

for the cables and secure the accessory-supplied junction

box cover (3000A or 3100A: Item 6) with accessory-

supplied M6 screws.

24. Run the plug end of the accessory-supplied transducer

wire harness back to the cooler. Connect the “SPTA” plug

into the circuit A transducer. Connect the “SPTB” plug

into the circuit B transducer. See Fig. 13.

25. Charge the unit to the amount of refrigerant as specified

on the 30XA base unit nameplate. Because of longer

field-installed liquid, economizer, and suction lines, addi-

tional charge is needed. Refer to Table 7 to calculate the

additional charge for each circuit and then add it to the

nameplate charge. Additional charge for the economizer

line is NOT required.

26. Perform all pre-start-up and start-up procedures specified

in the unit operation instructions. Follow the checklist

provided with the unit operation instructions.

27. Verify unit operation.