Fig. 37 -- Burner Flame

Heading South for the Winter?

Don’t Forget Your Furnace!

UNIT AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to the

furnace and other property damage.
If the furnace is installed in an unconditioned space where

the ambient temperatures may be 32_F or lower, freeze

protection measures must be taken to prevent minor

property or product damage.

CAUTION

!

Since the furnace uses a condensing heat exchanger, some water

will accumulate in the unit as a result of the heat transfer process.

Therefore, once it has been operated, it cannot be turned off and
left off for an extended period of time when temperatures will

reach 32_F or lower unless winterized. Follow these procedures
to winterize your furnace:

1. Obtain propylene glycol (RV/swimming pool antifreeze or

equivalent).

UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the

furnace and other property damage.
Do not use ethylene glycol (Prestone II antifreeze coolant or

equivalent). Failure of plastic components may occur.

CAUTION

!

2. Turn off electrical supply to the furnace. (See Fig. 19.)
3. Remove main furnace door. (See Fig. 22.)
4. Remove upper inducer housing drain connection cap.

(See Fig. 38.)

A06456

Fig. 38 -- Upper Inducer Housing Drain

Connection Cap

A06457

Fig. 39 -- Pour Antifreeze

5. Connect field--supplied 1/2--in. ID tube to upper inducer

housing drain connection.

6. Insert field--supplied funnel into tube.
7. Pour 1 quart of antifreeze into funnel/tube. Antifreeze

should run through inducer housing, overfill condensate
trap, and flow into open field drain. (See Fig. 39.)

8. Remove funnel and tube from inducer housing and replace

drain connection cap and clamp.

9. Replace main furnace door. (See Fig. 33.)

10. Propylene glycol need not be removed before restarting

furnace.