Carrier AQUAFORCE 30XA080-500 User Manual
Page 69
69
Table 7 — 30XA140-500 Electrical Data, Single Point (High Ambient Option)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit ter-
minals is not below or above the listed minimum and maximum limits. Maximum allow-
able phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage)
to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps
is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps
is 250 kcmil to 500 kcmil.
5. Data provided circuit 1/circuit 2 where there are two circuits.
UNIT
30XA
UNIT VOLTAGE
NUMBER
OF
COND
FANS
NO HYDRONIC PACKAGE
5 HP PUMP, 3450 RPM
7.5 HP PUMP, 3450 RPM
CONTROL CIRCUIT
V-Hz
(3 Ph)
Supplied
MCA
MOCP
ICF
Rec
Fuse
Size
MCA
MOCP
ICF
Rec
Fuse
Size
MCA
MOCP
ICF
Rec
Fuse
Size
Voltage
1 PH,
60 Hz
MCA
and
MOCP
Min Max
WD
XL
WD
XL
WD
XL
140
230-60
207
253
10
562.0
800
838.9
—
700
578.0
800
854.9
—
700
585.2
800
862.1
—
700
115
40
200-60
187
220
10
618.8
800
952.8
—
700
636.5
800
970.5
—
800
644.4
800
978.5
—
800
115
40
460-60
414
506
10
281.0
400
419.5
1051.5
350
289.0
400
427.5
1059.5
350
292.6
400
431.1
1063.1
350
115
40
575-60
518
633
10
216.3
300
332.5
838.5
250
222.7
300
338.9
844.9
250
225.6
300
341.8
847.8
250
115
40
380-60
342
418
10
328.3
450
504.6
1269.6
400
338.0
450
514.3
1279.3
400
342.3
450
518.7
1283.7
400
115
40
160
230-60
207
253
10
642.7
800
1036.7
—
800
658.7
800
1052.7
—
800
665.9
800
1059.9
—
800
115
40
200-60
187
220
10
706.9
1000
1179.4
—
800
724.5
1000
1197.1
—
1000
732.5
1000
1205.0
—
1000
115
40
460-60
414
506
10
320.5
450
518.0
1326.0
400
328.5
450
526.0
1334.0
400
332.1
450
529.6
1337.6
400
115
40
575-60
518
633
10
247.2
350
412.1
1058.1
300
253.6
350
418.5
1064.5
300
256.5
350
421.4
1067.4
300
115
40
380-60
342
418
10
374.9
500
622.8
1601.8
450
384.6
500
632.5
1611.5
450
388.9
500
636.8
1615.8
450
115
40
180
230-60
207
253
12
703.9
800
980.8
—
800
—
—
—
—
—
—
—
—
—
—
115
40
200-60
187
220
12
775.0
1000
1109.1
—
1000
—
—
—
—
—
—
—
—
—
—
115
40
460-60
414
506
12
351.9
450
490.4
1122.4
400
—
—
—
—
—
—
—
—
—
—
115
40
575-60
518
633
12
271.1
350
387.3
893.3
300
—
—
—
—
—
—
—
—
—
—
115
40
380-60
342
418
12
410.8
500
587.2
1352.2
450
—
—
—
—
—
—
—
—
—
—
115
40
200
230-60
207
253
12
795.6
1000
1189.6
—
1000
—
—
—
—
—
—
—
—
—
—
115
40
200-60
187
220
12
875.0
1200
1347.5
—
1000
—
—
—
—
—
—
—
—
—
—
115
40
460-60
414
506
12
396.9
500
594.4
1402.4
450
—
—
—
—
—
—
—
—
—
—
115
40
575-60
518
633
12
305.8
400
470.7
1116.7
350
—
—
—
—
—
—
—
—
—
—
115
40
380-60
342
418
12
463.8
600
711.7
1690.7
600
—
—
—
—
—
—
—
—
—
—
115
40
220
230-60
207
253
13
876.7
1200
1200.4
—
1000
—
—
—
—
—
—
—
—
—
—
115
40
200-60
187
220
13
964.6
1200
1359.4
—
1200
—
—
—
—
—
—
—
—
—
—
115
40
460-60
414
506
13
438.0
600
599.8
1407.8
500
—
—
—
—
—
—
—
—
—
—
115
40
575-60
518
633
13
337.6
450
475.0
1121.0
400
—
—
—
—
—
—
—
—
—
—
115
40
380-60
342
418
13
511.5
700
718.3
1697.3
600
—
—
—
—
—
—
—
—
—
—
115
40
240
230-60
207
253
13
933.0
1200
1256.7
—
1200
—
—
—
—
—
—
—
—
—
—
115
40
200-60
187
220
13
1026.7
1200
1421.6
—
1200
—
—
—
—
—
—
—
—
—
—
115
40
460-60
414
506
13
466.5
600
628.3
1436.3
600
—
—
—
—
—
—
—
—
—
—
115
40
575-60
518
633
13
359.5
450
497.0
1143.0
400
—
—
—
—
—
—
—
—
—
—
115
40
380-60
342
418
13
544.4
700
751.2
1730.2
600
—
—
—
—
—
—
—
—
—
—
115
40
260
460-60
414
506
15
529.1
700
806.6
2028.6
600
—
—
—
—
—
—
—
—
—
—
115
40
575-60
518
633
15
407.4
500
639.7
1617.7
500
—
—
—
—
—
—
—
—
—
—
115
40
380-60
342
418
15
616.7
800
969.3
2448.3
700
—
—
—
—
—
—
—
—
—
—
115
40
280
460-60
414
506
16
563.0
800
840.5
2062.5
700
—
—
—
—
—
—
—
—
—
—
115
40
575-60
518
633
16
433.6
600
665.9
1643.9
500
—
—
—
—
—
—
—
—
—
—
115
40
380-60
342
418
16
656.2
800
1008.8
2487.8
800
—
—
—
—
—
—
—
—
—
—
115
40
300
460-60
414
506
16
619.6
800
840.5
2062.5
700
—
—
—
—
—
—
—
—
—
—
115
40
575-60
518
633
16
476.7
600
665.9
1643.9
600
—
—
—
—
—
—
—
—
—
—
115
40
380-60
342
418
16
722.3
1000
1008.8
2487.8
1000
—
—
—
—
—
—
—
—
—
—
115
40
325
460-60
414
506
18
638.1
800
915.6
2137.6
700
—
—
—
—
—
—
—
—
—
—
115
40
575-60
518
633
18
491.2
600
723.5
1701.5
600
—
—
—
—
—
—
—
—
—
—
115
40
380-60
342
418
18
743.0
1000
1095.6
2574.6
1000
—
—
—
—
—
—
—
—
—
—
115
40
350
460-60
414
506
18
694.6
800
915.6
2137.6
800
—
—
—
—
—
—
—
—
—
—
115
40
575-60
518
633
18
534.2
700
723.5
1701.5
600
—
—
—
—
—
—
—
—
—
—
115
40
380-60
342
418
18
809.1
1000
1095.6
2574.6
1000
—
—
—
—
—
—
—
—
—
—
115
40
400
460-60
414
506
20
760.8
1000
1038.3
2260.3
1000
—
—
—
—
—
—
—
—
—
—
115
50
575-60
518
633
20
585.7
700
818.1
1796.1
700
—
—
—
—
—
—
—
—
—
—
115
50
380-60
342
418
20
886.5
1000
1239.1
2718.1
1000
—
—
—
—
—
—
—
—
—
—
115
50
450
460-60
414
506
22
889.1
1000
1110.0
2332.0
1000
—
—
—
—
—
—
—
—
—
—
115
50
575-60
518
633
22
683.4
800
872.7
1850.7
800
—
—
—
—
—
—
—
—
—
—
115
50
380-60
342
418
22
1035.9
1200
1322.4
2801.4
1200
—
—
—
—
—
—
—
—
—
—
115
50
500
460-60
414
506
22
937.6
1200
1158.5
2380.5
1200
—
—
—
—
—
—
—
—
—
—
115
50
575-60
518
633
22
720.8
800
910.0
1888.0
800
—
—
—
—
—
—
—
—
—
—
115
50
380-60
342
418
22
1092.4
1200
1378.8
2857.8
1200
—
—
—
—
—
—
—
—
—
—
115
50
ICF
— Instantaneous Current Flow
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
WD
— Wye-Delta
XL
— Across-the-Line