Caution – Carrier AQUAFORCE 30XA080-500 User Manual
Page 41
41
RIGGING UNIT (See Fig. 16-18) — The 30XA080-500 units
are designed for overhead rigging and it is important that this
method be used. Holes are provided in frame base channels,
marked for rigging (see rigging label on unit). Field-supplied
shackles are required to facilitate lifting. Secure the shackles
to the base rails at the points noted on the rigging label. See
Table 2 for the number of lifting points for each unit.
Do not use a forklift truck to move the units.
Use spreader bars to keep cables or chains clear of unit sides.
As further protection plywood sheets may be placed against
sides of unit, behind cables or chains. Run cables or chains to a
central suspension point so that angle from horizontal is not less
than 45 degrees. Raise and set unit down carefully.
See Fig. 16-18 for rigging centers of gravity.
For shipping, some domestic units and all export units are
mounted on a wooden skid under entire base of unit. Skid can
be removed before unit is moved to installation site. Lift the
unit from above to remove skid. See Fig. 16-18 for rigging
center of gravity. On export units, the top skid can be used as
the spreader bars. If the unit was shipped with a shipping bag,
the bag must be removed to gain access to the rigging holes in
the base rail.
If overhead rigging is not available, the unit can be moved
on rollers or dragged. When unit is moved on rollers, the unit
skid, if equipped, must be removed. To lift the unit, use jacks at
the rigging points. Use a minimum number of rollers to distrib-
ute the load such that the rollers are no more than 6 ft (1.8 m)
apart. If the unit is to be dragged, lift the unit as described
above, and place unit on a pad. Apply moving force to the pad,
and not the unit. When in its final location, raise the unit and
remove the pad. If the unit was shipped with coil protection, it
must be removed before start-up. The shipping bag for export
units must be removed before start-up.
Step 3 — Cooler Fluid and Drain Piping Con-
nections —
See Fig. 19-22 for piping applications.
GENERAL — The factory-installed victaulic connections al-
low clamp-on connection of water lines to the coolers in all
30XA units. A flow sensor is factory-installed in the side of the
entering fluid nozzle. See Fig. 23. See Table 3 for 30XA unit
operating range. See Fig. 20 for cooler option dimensions.
DUAL PUMP UNITS — ENGLISH
DUAL PUMP UNITS — SI
*Condenser Coil: Copper Fins/Copper Tubing.
30XA
UNIT SIZE
MOUNTING WEIGHT (lb) — Cu/Cu*
A
B
C
D
E
F
Total
090
1394
3347
1369
1093
2330
1392
10,924
100
1420
3409
1406
1117
2382
1418
11,151
110
1433
3452
1428
1139
2416
1424
11,291
120
1467
3491
1430
1142
2449
1458
11,436
30XA
UNIT SIZE
MOUNTING WEIGHT (lb) — Cu/Cu*
A
B
C
D
E
F
G
H
Total
140
2188
1735
2012
1889
1273
1004
1876
1990
13,966
160
2242
1762
2029
1919
1299
1019
1896
2043
14,209
30XA
UNIT SIZE
MOUNTING WEIGHT (kg) — Cu/Cu*
A
B
C
D
E
F
Total
090
632
1518
621
496
1057
631
4955
100
644
1546
638
507
1080
643
5058
110
650
1566
648
517
1096
646
5122
120
665
1583
649
518
1111
661
5187
30XA
UNIT SIZE
MOUNTING WEIGHT (kg) — Cu/Cu*
A
B
C
D
E
F
G
H
Total
140
992
787
913
857
577
455
851
903
6335
160
1017
799
921
871
589
462
860
927
6445
30XA090-120
30XA140,160
Fig. 15C — Unit Mounting Weights (Units with Cu/Cu Condenser Coils) (cont)
a30-4420
a30-4421
A
B
C
F
E
D
COOLER SIDE
COMPRESSOR SIDE
A
B
C
D
H
G
F
E
COOLER SIDE
COMPRESSOR SIDE
CAUTION
Remove the chilled water flow switch, entering and leaving
water thermistors before welding connecting piping. Rein-
stall flow switch and thermistors after welding is complete.
Failure to remove these devices may cause unit damage.