STEP 1
Locate vent opening on the wall. To locate hole center
consult with appropriate fireplace dimensions, Page 4.
Frame as shown below.
Combustible Walls (Fig. 17): Cut a 10³⁄₈”H x 9³⁄₈” W
(264 x 240 mm) hole through the exterior wall and
frame as shown.
Noncombustible Walls (Fig. 17): Hole opening must
be 7¹⁄₂” (190 mm) in diameter.

Always use a zero clearance sleeve when
the wal is combustible.

STEP 2
Measure wall thickness and cut zero clearance sleeve
parts to proper length (MAXIMUM 12”/305 mm). Assem-
ble sleeve and attach to firestop with #8 sheet metal
screws (supplied). (Fig. 18)
STEP 3
Measure the horizontal length requirement for the vent-
ing including a 2” (51 mm) overlap, i.e. from the elbow
to the outside wall face plus 2” (51 mm). (Fig. 15 or 16)

attach the elbow to the appliance in the same manner
then attach the venting to the elbow.

Never permit a downward slope (away from
the fireplace) to occur anywhere in the sys-
tem when installing the vent or an elbow in
the vent.

STEP 5
Guide the venting through the vent hole a you place the
appliance in its installed position. Guide the 4” (102 mm)
and 7” (178 mm) collar of the vent termination into the
outer ends of the venting. Do not force the termination. If
the vent pipes do not align with the termination, remove
and realign the venting at the appliance flue collars.
(Fig. 19) Attach the termination to the wall as outlined in
the instruction sheet supplied with the termination.

FP1005
Side View Vent Termination
1/25/00 djt

Finished Wall

Vent

Termination

FP1753

Fig. 19 Side view of final unit location.

Firestop

Zero Clearance

Sleeve

Rear Wall Installation

Twist Lock Pipe

FP1751
vent opening
2/07

Vent Opening for Combustible Wall

9³⁄₈”

(240mm)

10³⁄₈”

(264mm)

Fireplace Hearth

Framing

Detail

Opening for

Noncombustible Wall

7¹⁄₂”

(190 mm)

FP1751

Fig. 17 Locate vent opening on wall.

Firestop

Top Tabs

Bottom Tabs

Install provided firestop with zero

clearance sleeve into framing

opening after drywall or finish

material is installed. Use the tabs

for clearance locators top and

bottom.

Maintain 1” (25 mm) Air

Space from Zero Clear-

ance Sleeve to Framing

FP1752
Zero Clearance Sleeve
2/07

Max. Length

12” (305mm)

#8 Screws (2)

#8 Screws

(2)

Adjustable
Zero Clear-
ance Sleeve

#8 Screws

(2)

Adjust-

able Zero

Clearance

Sleeve

FP1752

Fig. 18 Adjustable zero clearance sleeve.

Firestop

1” (25 mm) Clear-

ance between Zero

Clearance Sleeve

and Framing

STEP 4
Install the 4” (102 mm) vent to the appliance collar and
secure with three (3) sheet metal screws. Install the 7”
(178 mm) vent pipe to the appliance collar and secure
with three (3) sheet metal screws. It is not necessary
to seal this connection. If a 45° elbow is being used,

Vertical Sidewall Applications

Since it is very important for the venting system
to maintain balance between the combustion air
intake and the flue gas exhaust, certain limitations
as to vent configurations apply and must be strictly
adhered to.