Sentinel Product Dosing Information
Technical Instruction Document
TID-0025_0B
10/16/13
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Page 2 of 4
X300– System Cleaner
APPLICATION:
To clean a new system, or a system up to six months old, Sentinel X300 should be
circulated with all valves open for a minimum period of one hour. Warming the water will aid the process.
No neutralisation procedure is required. After cleaning, the system should be drained and then thoroughly
flushed through ALL drain points. Refill and treat with Sentinel X100 Inhibitor or Sentinel X500 Inhibited
Antifreeze. Sentinel X300 is suitable for use with all commonly encountered metals and alloys, including
aluminum.
DOSE RATE:
Sentinel X300 should be dosed at 1% of system volume, i.e., 1 Quart per 25 Gallons of
system water. For larger systems, additional X300 will be required. Overdosing does not present a
problem. Please note: Where a thermal storage appliance is fitted, allowance must be made for the
increased volume of primary water.
DOSING INSTRUCTIONS:
Open vented systems: Dose via F&E cistern (sufficient draining from a low
point is required to ensure that all of the product enters the circulating part of the system), or use a dosing
bottle. Sealed systems: If the system is empty, add to any convenient point before filling. If full, use a
dosing bottle to inject via the filling loop or other access point.
X400 – System Restorer
APPLICATION:
To clean an older system Sentinel X400 should be circulated, preferably at normal
operating temperature, with all valves open for a minimum period of two hours or until satisfactory
performance is restored. Where systems are badly fouled, a longer period of circulation (up to four weeks)
is recommended. Alternatively, more rapid and effective cleaning will result if Sentinel X400 is used in
conjunction with a power flushing device. No neutralisation procedure is required. After cleaning, the
system should be drained and then thoroughly flushed through ALL drain points. Refill and treat with
Sentinel X100 Inhibitor or Sentinel X500 Inhibited Antifreeze. Sentinel X400 is ideal for use where a new
boiler or pump is to be fitted to an existing system or where radiators have cold areas due to sludge build
up. It is suitable for use with all commonly encountered metals and alloys, including aluminum.
DOSE RATE:
Sentinel X400 should be dosed at 1% of system volume, i.e., 1 Quart per 25 Gallons of
system water. For larger systems, additional X400 will be required. Overdosing does not present a
problem. Please note: Where a thermal storage appliance is fitted, allowance must be made for the
increased volume of primary water.
DOSING INSTRUCTIONS
: Open vented systems: Dose via F&E cistern (sufficient draining from a low
point is required to ensure that all of the product enters the circulating part of the system), or use a dosing
bottle. Sealed systems: If the system is empty, add to any convenient point before filling. If full, use a
dosing bottle to inject via the filling loop or other access point.
DO NOT ADD TO PRIMATIC SYSTEMS