beautypg.com

Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA User Manual

Page 8

background image

10. Replace main furnace door.

Step 7—Electrical Controls and Wiring

There may be more than 1 electrical supply to the unit. Check
accessories and cooling unit for additional electrical supplies.

The electrical ground and polarity for 115-v wiring must be
maintained properly. Refer to Fig. 11 for field wiring information
and to Fig. 15 for unit wiring information.

NOTE:

If the polarity is not correct, the STATUS LED on the

control center will flash rapidly and prevent the furnace from
operating. The control system also requires an earth ground for
proper operation of the control center and flame sensing.

The 24-v circuit contains an automotive-type, 3-amp fuse located
on the control center. (See Fig. 12.) Any direct shorts of the 24-v
wiring during installation, service, or maintenance will cause this
fuse to blow. If fuse replacement is required, use ONLY a fuse of
identical size.

With power to the unit disconnected, check all electrical connec-
tions for tightness. Tighten all screws on electrical connections. If
any smoky or burned connections are found, disassemble the
connection, clean all parts, strip wire, and reassemble properly and
securely.

Reconnect electrical supply to unit and observe unit through 1
complete operating cycle. Electrical controls are difficult to check
without proper instrumentation; if there are any discrepancies in
the operating cycle, contact your dealer and request service.

Step 8—Troubleshooting

For an explanation of status codes, refer to service label located on
back of main furnace door or Fig. 16, and the Troubleshooting
Guide.

The control center stores 1 status code (representing the last fault
to occur) for a period of 48 hr or until the 115- or 24-v power is
interrupted.

NOTE:

Removing blower access panel will open blower access

panel door switch and terminate 115-v power to control center.
The status code will be erased. Look into blower access panel sight
glass for current LED status BEFORE removing blower access
panel.

The unit’s component test is a useful troubleshooting tool since it
displays the current status code of the furnace and functionally
operates all furnace components except the gas valve. The com-
ponent test and methods to initiate it are described below.

COMPONENT TEST SEQUENCE

NOTE:

All components are functionally operated except the gas

valve.

When component test is initiated, the following sequence of events
occurs:

1. LED flashes a status code 4 times.

2. Inducer motor starts and continues to run for remainder of

component test.

3. Hot surface ignitor is energized for 15 sec, then de-energized.

4. Main blower operates at cooling speed for 10 sec, then turns

off.

5. Main blower operates at heating speed for 10 sec, then turns

off.

6. Inducer motor stops.

Component test can be initiated by one of the following proce-
dures.

INITIATING COMPONENT TEST AND RETRIEVING STA-
TUS CODE BY REMOVING MAIN LIMIT SWITCH WIRE

NOTE:

NO thermostat signal may be present at control center

and all blower time delay off periods must be completed.

Fig. 11—Field Wiring

A98325

115-V

FIELD-SUPPLIED

DISCONNECT

SWITCH

115-V

SINGLE

PHASE

AUXILIARY
J-BOX

FURNACE

CONTROL

CENTER

TWO WIRE

24-V

TERMINAL

BLOCK

THREE-WIRE

HEATING

ONLY

FIVE

WIRE

NOTE 5

NOTE 1

NOTE

3

THERMOSTAT
TERMINALS

FIELD-SUPPLIED

DISCONNECT

CONDENSING

UNIT

R

W2

W

C

R

G

Y

GND

GND

GND

GND

FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-, 208/230-, 460-V WIRING

208/230- OR

460-V

THREE PHASE

208/230-V

SINGLE

PHASE

W/W1

Y/Y2

G

C

NOTES:

1.
2.
3.
4.

5.

Connect Y or Y/Y2 terminal as shown for proper cooling operation.
Proper polarity must be maintained for 115-v wiring.
Use W2 with 2-stage thermostat when zoning.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
Some thermostats require a "C" terminal connection as shown.

8