Step 1—Cleaning and/or Replacing Air Filter
The air filter arrangement may vary depending on the application
or orientation.
Never operate unit without a filter or with the blower access
panel removed. Failure to follow this warning could result in
a fire or personal injury.
To clean or replace the filters, proceed as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Release filter retainer wire. (See Fig. 3 and 4.)
4. Slide filter out of furnace.
5. Furnaces are equipped with permanent, washable filter(s).
Clean filter by spraying cold tap water through filter in
opposite direction of airflow.
6. Rinse filter and let dry. Oiling or coating of filter is not
recommended.
7. Place filter in furnace.
8. Replace blower access panel and main furnace door.
9. Turn on electrical supply to furnace.
NOTE:
If the filter has cross-mesh binding, the binding must face
the blower. If the filter has an air direction arrow, the arrow must
point toward the blower.
Step 2—Blower Motor and Wheel Maintenance
To ensure long life, economy, and high efficiency, clean accumu-
lated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no
additional lubrication. These motors can be identified by the
absence of oil ports on each end of the motor.
The following items should be performed by a qualified service
technician.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Disconnect wires.
All factory wires can be left connected, but field thermostat
connections may need to be disconnected depending on their
length and routing.
4. Position control box, transformer, and door switch assembly to
right side of furnace casing.
5. If condensate trap is located in left- or right-hand side of
furnace casing, proceed to item 6, otherwise remove trap and
tubing as described below.
a. Disconnect field drain connection from condensate trap.
b. Disconnect drain and relief port tubes from condensate
trap.
c. Remove condensate trap from blower shelf.
6. Remove screws securing blower assembly to blower shelf and
slide blower assembly out of furnace.
7. Clean blower wheel and motor by using a vacuum with soft
brush attachment. Be careful not to disturb balance weights
(clips) on blower wheel vanes. Do not bend wheel or blades as
balance will be affected.
8. If greasy residue is present on blower wheel, remove wheel
from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly to
ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE:
Mark blower mounting arms and blower housing so each
arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate location to
ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing and
slide motor and mounts out of housing. Disconnect capaci-
tor and ground wire attached to blower housing before
removing motor.
f. Remove blower wheel from housing.
g. Clean wheel per instructions on degreaser cleaner.
9. Reassemble motor and blower wheel by reversing items 8b
through 8f. Ensure wheel is positioned for proper rotation. Be
sure to reattach ground wire.
10. Reinstall blower assembly in furnace.
Fig. 3—Bottom Filter Arrangement
A93046
WASHABLE
FILTER
FILTER
SUPPORT
FILTER
RETAINER
Fig. 4—Filter Installed for Side Inlet
A93045
FILTER
RETAINER
WASHABLE
FILTER