5| Commissioning
5.7 Avoiding liquid shocks
ATTENTION! Slugging can damage the compressor and cause refrigerant to
leak.
To prevent liquid shocks:
The complete refrigeration plant must be correctly designed and executed.
The capacities of all components must be compatible (particularly evaporator
and expansion valve).
Suction gas superheating at the evaporator output should be at least 7
– 10 K (check setting
of the expansion valve).
The system must reach a state of equilibrium.
Particularly in critical systems (e.g. several evaporator points), suitable measures, e.g.
use of liquid traps, solenoid valve in the liquid line, etc. are recommended.
See also other documents in the category GEA Bock Air equipment:
- HG5 (32 pages)
- HG7 (34 pages)
- HG4 (32 pages)
- HG6 (32 pages)
- HG8 (38 pages)
- HG34e (30 pages)
- HG22Р (26 pages)
- HG12Р (26 pages)
- BCM2000 (18 pages)
- HG22e (26 pages)
- HG34P (26 pages)
- HG88e (38 pages)
- HG44e (34 pages)
- HА4 (32 pages)
- HА34P (26 pages)
- HA12P (26 pages)
- HA5 (32 pages)
- HA6 (32 pages)
- HG22Р CO2 (28 pages)
- HG34P CO2 (28 pages)
- HG4 CO2 (30 pages)
- HG12Р CO2 (28 pages)
- HG12e CO2 (28 pages)
- HGX2 CO2 T (28 pages)
- HGX34 CO2 T (40 pages)
- HGX46 CO2 T (40 pages)
- HAX2 CO2 T (28 pages)
- HG5 R134a (32 pages)
- HG6 R134a (32 pages)
- HG7 R134a (32 pages)
- HG4 R134a (32 pages)
- HGZ7 (42 pages)
- F (44 pages)
- F18 (28 pages)
- FK40 (26 pages)
- FK30 (26 pages)
- FK50 (26 pages)
- HG22P A (28 pages)
- HG34e A (28 pages)
- HG22e A (28 pages)
- HGX34P 2 pole (32 pages)