4| Compressor assembly

4.7 Pipes

Pipes and system components must be clean and dry inside and free of scale, swarf and layers

of rust and phosphate. Only use air-tight parts.

Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being

cracked and broken by severe vibrations.

Ensure a proper oil return.
Keep pressure losses to an absolute minimum.

4.6 Pipe connections

Valve spindle seal

4.8 Operating the shut-off valves

Before opening or closing the shut-off valve, release the valve spindle seal by approx. ¼ of a turn

counter-clockwise.

After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.

Fig. 13

Fig. 14

ATTENTION! Overheating can damage the valve.

Solder only using inert gas to inhibit oxidation products.

Release

Tighten

The

pipe connections have graduated inside diameters so that pipes

in the common millimeter and inch dimensions can be used.

The connection diameters of the shut-off valves are designed for

maximum compressor output.

The required pipe cross-section must

be matched to the capacity. The same applies for non-return
valves.

Fig. 12: Stepped
internal diameters