HEATING CYCLE ANALYSIS
COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (GPM) x
TEMP. DIFF. (DEG. F) x
FLUID FACTOR* =
(Btu/hr)
SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
=
(DEG F)
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
=
(DEG F)
*Use 500 for water, 485 for antifreeze.
a50-8445
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXPANSION
VALVE
F
F
AIR
COIL
F
PSI
WATER OUT
WATER IN
F
PSI
LOOK UP PRESSURE DROP IN TABLE 26
TO DETERMINE FLOW RATE
F
LIQUID LINE
PSI
F
SAT
a50-8446
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXP ANSION
VA LV E
°F
°F
AI R
COI L
°F
PSI
WA TER OUT
WA TER IN
°F
PSI
LOOK UP PRESSURE DROP IN T ABLE 26
TO DETERMINE FLOW RA TE
°F
LIQUID LIN E
PSI
°F
SA T
97B0038N05