A. Connect Fuel Lines

For oil supply system specifi cations for tanks not mounted
on machines, carefully follow the pump manufacturer’s
literature and the latest edition of the National Fire
Protection Association (NFPA) 31 standard.

Pumps with automatic bypass do
not require a bypass plug. Verify by

referring to the pump manufacturer’s instructions.

B. Fuel Supply Level with or Above Burner

The burner may be equipped with a single stage pump.
If a one-pipe system is installed, verify a bypass plug is

not installed in the pump, then connect the fuel supply
to the burner with a single supply line Note that manual
bleeding of the pump is required on initial start-up or when
the equipment runs out of fuel. When connecting a two-
pipe fuel system, install the pump bypass plug.

C. Fuel Supply Below Level of Burner

Shutoff valves should be located in the oil supply line. Do
not install valves in the return line.

Section: Fuel Supply

Do Not Install Bypass Plug
with 1-Pipe System

Failure to comply could cause Immediate pump seal

failure, pressurized oil leakage and the potential for a

fi re and injury hazard.

y

The burner is shipped without the bypass plug installed.

y

Install the bypass plug in two-pipe oil supply systems
ONLY.

Oil Supply Pressure
Control Required

Damage to the fi lter or pump seals could cause oil

leakage and a fi re hazard.

y

The oil supply inlet pressure to the burner cannot

exceed 3 psig.

y

Ensure that a pressure limiting device is installed in

accordance with the latest edition of NFPA 31.

y

Do NOT install valves in the return line. (NFPA 31,

Chapter 8.)

y

Gravity Feed Systems: Always install an anti-siphon

valve in the oil supply line or a solenoid valve (RWB
Part # 22246U) in the pump/nozzle discharge tubing
to provide backup oil fl ow cut-off protection.

Do Not Use Tefl on Tape

Damage to the pump could cause impaired burner

operation, oil leakage and appliance soot-up.

y

Never use Tefl on tape on fuel oil fi ttings.

y

Tape fragments can lodge in fuel line components

and fuel unit, damaging the equipment and preventing

proper operation.

y

Use oil-resistant pipe sealant compounds.

When the fuel supply is more than eight feet below the level
of the burner, a two-pipe fuel supply system is required.
Depending on the fuel line diameter and the horizontal
and vertical length, the installation may also require a
two-stage pump. Consult the fuel unit manufacturer’s
literature for lift and vacuum capability.

D. Fuel Line Replacement (Remote Tank Only)

When replacing fuel lines, continuous lengths of heavy
wall copper tubing is recommended. To ensure a tight
seal, always use fl are fi ttings. Never use compression
fi ttings. Always install fi ttings in an accessible location. To
avoid vibration noise, fuel lines should not run against the
appliance or the ceiling joists.

E. Fuel Line Valve and Filter

The Beckett Z gauge (part number Z-
2000) is available to permit checking

the F head “Z” dimension without removing the burner.

Fuel Supply

tube installed but should always be verifi ed during service
and installation. If the “Z” dimension is out of adjustment,
perform the following steps.

Before proceeding, turn off power to the burner.

1. Disconnect the oil connector tube from the nozzle

line.

2. Referring to Figure 5, loosen the splined nut from

the nozzle line. Loosen the hex head screw securing
the escutcheon plate to the burner housing.

3. A Beckett T650 gauge should be used to set the Z

dimension.

4. Place the end of a ruler at the face of the nozzle and,

using a straight edge across the head, measure the
distance to the face of the head.

5. Slide the nozzle line forward or back until this

dimension for F heads is 1-1/8”.

6. Tighten the hex head screw to secure the escutcheon

plate to the burner chassis. Then tighten the splined
nut and attach the oil connector tube.

7. Recheck the “Z” dimension periodically when

servicing to ensure the escutcheon plate has not
shifted. You will need to reset the “Z” dimension if
you replace the air tube or nozzle line assembly.