beautypg.com

Rane CP 64 (2004-2006 version) User Manual

Page 7

background image

Manual-5

by the ZONE LEVEL control. Note the following:

• Zone Level, EQ and Limiter circuits do not affect Page signals

summed Post-VCA.

• Zone Level, EQ and Limiter circuits do affect Page signals

summed Pre-VCA.

• Page signals are not available on the Expand Zone output

when summed Post-VCA.

• Page signals are always available for the Expand Page output.

There are two internal controls related to the Program Priority

detector:

• Priority Release Time

2 sec to 20 sec (trim pot)

Default: 12 seconds

• Priority Threshold

-∞ to -35 dBu (trim pot)

Default: -50 dBu

The default settings for the Program Priority detector are

chosen for most applications. Detector Threshold settings lower

than the default setting of -50 dBu are prone to false trigger-

ing unless the source is very quiet. If a source is noisy, you may

wish to set the threshold higher to prevent false triggering. The

default Release Time is 12 seconds. You may wish to decrease

the Release Time if the source is a TV, radio, tape machine or

any other relatively constant signal source. If you have a source

like a jukebox, with relatively long search times, you may wish to

extend the Release Time.

There is one internal control related to Zone 1:

• Zone 1 Mode

Mono/Stereo

Default: Stereo

CP 64 CONNECTIONS

Power to the CP 64 should be OFF until all connections are made.

EUROBLOCK CONNECTIONS

All Input and Output connections are made with Euroblock

connectors except for the RCA Program Inputs. When wiring to

Euroblocks, a minimum wire gauge of 22 is preferred for reliabil-

ity. If the ground or shield wire is left shorter, it acts as a strain

relief for the other wires. Cable with a flexible jacket is easier to

use and less likely to damage the connections. Avoid stripping

excess insulation. Inspect wires for nicks that may lead to wire

breakage. Fully insert each wire in the appropriate socket and

tighten the screw.

Page Input circuits are true instrumentation amplifier inputs

and operate balanced or unbalanced. Expand and Zone Outputs

are driven by high quality cross-coupled line drivers and operate

balanced or unbalanced. For both Inputs and Outputs, wiring

is basically the same. Balanced operation is recommended. Bal-

anced wiring is straight forward, (+) to (+), (–) to (–) and shield

to shield.

For unbalanced operation, we recommend using two conduc-

tor cable with shield. The cable is wired to the CP 64 the same

as for balanced operation. At the other end of the cable, connect

the (+) wire to signal “hot” and both the (–) and shield wires to

ground (important.)

If you use single conductor cable with shield, connect the

shield/gnd wire to both the (–) and shield pins at the CP 64. At

the other end of the cable connect the (+) wire to the signal “hot”

and the shield/gnd wire to ground. When unbalanced wiring

is used, it is very important for the CP 64 and any other unit

in the system to have good earth or technical grounds. If a unit

is located far from the CP 64 or is of a type that might create

grounding problems, isolation transformers should be used.

When operating cross-coupled line drivers unbalanced (i.e., any

CP 64 Output), it is essential to ground the (–) pin.

PROGRAM INPUTS

The four stereo Program Inputs connect to RCA jacks. These

Inputs are unbalanced. The same guidelines given above for

unbalanced operation apply to these Inputs.

Refer to the RaneNote, “Sound System Interconnection“

(included) for additional wiring information.

REMOTE INSTALLATION

The CP 64 supports wired remotes for Page Assign, Zone

Level and Zone Source selection. Wire lengths of up to 1000 feet

are possible. A brief list of suitable wire types is provided in the

WIRE TYPES section on the next page.

The PR 2 remote provides Page Zone Assign for Page 1 and

Page 2 signals and is usually located at the Page source. If your

application requires one of the two PAGE ASSIGN switches to

control both Page 1 and Page 2 Assign, simply wire all Page 1

and Page 2 control bits in parallel. You may wish to leave the

knob off the unused control and cover it with one of the hole

plugs provided in the kit. If your installation requires Page 1 and

Page 2 remote control at two different locations, only three wires

are required for each PR 2 remote (Z1, Z2 & GND). As above,

you may wish to leave the knob off the unused control and cover

it with a hole plug.

The ZR 1 remote provides Zone Level and Source Selection,

allowing local control from inside the Zone. Two ZR 1 remotes

may be used (only use one in each Zone). If only one of the two

controls is used, you may wish to cover the unused control with

one of the hole plugs provided in the kit. If you require one ZR 1

remote to control both Zones, simply wire the ports in parallel.

This may be done with Program Select only, Level only or both.

If only one of the two controls is wired in parallel, the other is

still available for a second remote.

When paralleling one remote across multiple CP 64s, all

three control pins must be wired, including the shields.

Power to the CP 64 should be off until all connections are

made. It is important to ensure that the CP 64 Remote Ports are

not subjected to sustained voltages outside the range of 0 to 5

volts DC or high levels of static. Inputs are protected, however,

caution is the better part of… you know. It is a good idea to

install the wiring, connect it to the remote assemblies and then

make the final connections at the CP 64. Do not short Vr1 or

Vr2 pins to ground. These pins are current limited, however, ex-

cess heat is generated in the 5 volt supply if a short occurs. Never

subject the Vr1 or Vr2 pins to voltages above 5 volts.