TTW SERVICE PROCEDURE VIII

Safety Circuit Voltage Trace

Safety Circuit Voltage

Trace

WARNING

115 volt potential exposure. Use caution

making voltage checks to avoid personal injury.

Position gas control switch to the “ON”

position and adjust thermostat dial to call

for heat, Is there 10 to 13 VAC between

red wire leading to blower temperature

switch and green ground wire?

Blower must be running during this

voltage check.

(see photo 27)

Red wire leading to

blower temp. switch

Green ground wire

27

Yellow wire

leading from

pressure switch

Y

Is there 10 to 13 VAC between yellow

wire leading from pressure switch and

green ground wire?

(see photo 27)

Do you hear or can you

see the igniter sparking?

Y

Y

Is LED on gas valve flashing

the “heartbeat” code

(alternating bright/dim)

N

Safety circuit

voltage is OK.

No voltage from gas control,

call for technical support.

Y

NOTE: This procedure assumes a cool tank.

Verify 115VAC to gas

control (see page 30)

Is there continuity

through blower

temperature switch?

(see page 22)

Y

Check for loose or

broken wire

connection at switch

terminals

N

N

Determine cause of blower

temperature switch

activation and correct.

Check igniter/sensor

(see page 17)

is igniter/sensor OK?

If burner does not light,

observe LED flash code

on gas valve and refer to

troubleshooting section

on page 13

N

N

Page 29

26

Remove three screws (Phillips Screw driver) from control access

cover on blower and remove cover (see photo 26).

Faulty cord set or

gas control.

Y

Correct igniter/

sensor problem.

pg29.pdf 1