Troubleshooting – Bradford White TW4-75S-76B-3X User Manual

Page 14

background image

Six-four flash, three

second pause

Undesired-false

pilot flame

sensed.

System auto

resets.

Seven flash, three

second pause

Simulated

Resistive Device

Harness out of

specification.

Eight-one flash, three

second pause

Simulated

Resistive Device

Harness

specification

check.

Eight-two flash, three

second pause

Thermal well

sensor damaged

or unplugged

Eight-three flash, three

second pause

Gas valve

electronics fault

detected

LED Status

Control

Status

Service

Procedure

Probable Cause

Pilot valve stuck in open position.

Replace gas control,

page 26

Simulated resistive device out of specification.

Page 28

Simulated resistive device out of specification.

Page 28

1. Damage to thermal well wire.

2. Thermal well sensor resistance out of range.

Page 24

1. Control needs to be reset.

2. Control is wet or physically damaged.

1. Interrupt power supply

2. Replace gas control,

page 26

Eight-four flash, three

second pause

Gas valve fault

detected.

1. Control needs to be reset.

2. Control is wet or physically damaged.

1. Interrupt power supply

2. Replace gas control,

page 26

Troubleshooting

Six-three flash, three

second pause

Pilot flame

extinguished.

System auto

resets.

1. Unstable pilot.

2. Pilot tube blocked or restricted.

3. Oxidation build up on pilot electrode.

4. Wire damage to pilot assembly or bad

connection at gas valve.

5. Insufficient combustion air.

6. Gas pressure is out of specification.

1. Page 15

2-4. Page 17

5. Refer to installation manual

Page 14

Six-two flash, three

second pause

Pressure switch

or blower temp

switch opened

during burner

operation.

System auto

resets.

1. Check vent or vent tables.

2 & 3 Page 18

4. Refer to venting section of

installation manual

5. Page 20

6 & 7 Page 22

1. Vent blockage or improper vent configuration.

2. Pressure switch tubing kinked or blocked.

3. Faulty pressure switch.

4. Vent termination being affected by wind

5. Blower not spinning up to speed.

6. Blower temp or exhaust temp too high

7. Faulty blower temperature switch.

Six-one flash, three

second pause

Failed to light

pilot.

System auto

resets.

1. Unstable pilot.

2. Pilot tube blocked or restricted.

3. Oxidation build up on pilot electrode.

4. Wire damage to pilot assembly or bad

connection at gas valve.

1. Page 15

2-4. Page 17

pg14.pdf 1

pg14.pdf 1

3/24/06 4:07:05 PM

3/24/06 4:07:05 PM

Page 14