beautypg.com

38/ 40gx c (q ), Fig. 12 --- field wiring – Carrier 40GXQ User Manual

Page 8

background image

8

G

Terminal Block

Conduit panel

Conduit

Outdoor

unit

L

N

L

N

GND

S

L

N

GND

S

Ground

Control

Indoor Unit

Pow er

Ground

Control

Indoor

Pow er

38GXQ-40GXQ009, 012 115-1-60 Connection Diagram

All 40GXQ 115-1-60 Indoor Units

Supply

Unit

Supply

115-1-60

115-1-60

115-1-60

All 38GXQ 115-1-60 Outdoor Units

CONNECTING CABLE

OUTDOOR TO INDOOR

Main

Pow er to

L1

L2

L1

L2

GND

S

L1

L2

GND

S

Ground

Control

Ground

Control

All 38GXQ 208/230-1-60 Outdoor Units

All 40GXQ 208/230-1-60 Indoor Units

Supply

Unit

Supply

208/230-1-60

208/230-1-60

208/230-1-60

Pow er

Indoor

Pow er

38GXQ-40GXQ012, 018 & 024 208/230-1-60 Connection Diagram

CONNECTING CABLE

OUTDOOR TO INDOOR

Main

Pow er to

Indoor Unit

A09666

Fig. 12

--- Field Wiring

INSTALL ALL POWER, INTERCONNECTING

WIRING, AND PIPING TO INDOOR UNIT.

1. Run interconnecting piping and wiring from outdoor unit to

indoor unit.

2. Pass interconnecting cable through hole in wall (outside to

inside).

3. Lift indoor unit into position and route piping and drain

through hole in wall (inside to outside). Fit interconnecting

wiring into back side of indoor unit.

4. Hang indoor unit on upper hooks of wall mounting plate (as

shown in Fig. 13)

A08283

Fig. 13

--- Hanging Indoor Unit

5. Open front cover of indoor unit and remove field wiring ter-

minal block cover (see Fig. 14)

Field Wiring

Cover

Interconnecting

Cable

A08279

Fig. 14

--- Field Wiring Cover

6. Pull interconnecting wire up from back of indoor unit and

position in close to the terminal block on indoor unit.

7. Push bottom of indoor unit onto mounting plate to com-

plete wall mount.

8. Connect wiring from outdoor unit per connection diagram

(see Fig. 12).

NOTE:

Polarity of power wires must match original

connection on outdoor unit.

9. Replace field wiring cover and close front cover of indoor

unit.

10. Connect refrigerant piping and drain line outside of indoor

unit. Refer to Fig. 10 for proper installation of flare connec-
tions. Complete pipe insulation at flare connection then

fasten piping and wiring to the wall as required. Com-
pletely seal the hole in the wall.

38/

40GX

C

(Q

)