beautypg.com

Warning, Caution, Safety considerations – Carrier 40GXQ User Manual

Page 3: General, System requirements

background image

3

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air--conditioning equipment
can be hazardous due to system pressures, electrical components,

and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should

install, start--up, and service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning coils. All other operations should be performed by

trained service personnel.
When working on the equipment, observe precautions in the

literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep

quenching cloth and fire extinguisher nearby when brazing. Use
care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit. Consult

local building codes and current editions of the National Electrical

Code ( NEC ) NFPA 70. In Canada, refer to current editions of the
Canadian electrical code CSA 22.1.

Recognize safety information. This is the safety--alert symbol

!!

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.Understand

these signal words: DANGER, WARNING, and CAUTION.
These words are used with the safety--alert symbol. DANGER

identifies the most serious hazards which will result in severe

personal injury or death. WARNING signifies hazards which

could result in personal injury or death. CAUTION is used to

identify unsafe practices which may result in minor personal injury
or product and property damage. NOTE is used to highlight

suggestions which will result in enhanced installation, reliability, or

operation.

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF

position. There may be more than 1 disconnect switch.

Lock out and tag switch with a suitable warning label.

CAUTION

!

EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe

in the ground. If any section of pipe is buried, there must be

a 6 in. (152 mm) vertical rise to the valve connections on

the outdoor units. If more than the recommended length is

buried, refrigerant may migrate to the cooler buried section

during extended periods of system shutdown. This causes

refrigerant slugging and could possibly damage the

compressor at start--up.

GENERAL

These instructions cover the installation, start--up and servicing of
38GXC(Q) outdoor and 40GXC(Q) indoor units duct free systems.

SYSTEM REQUIREMENTS

Allow sufficient space for airflow and servicing unit. See Fig. 2
and 3 for minimum required distances between unit and walls or

ceilings.
Piping
IMPORTANT
: Both refrigerant lines must be insulated
separately.
S

Minimum refrigerant line length between the indoor and outdoor

units is 10 ft. (3 m).

S

The following maximum lengths are allowed:

REFRIGERANT LINE LENGTHS ft. (m)

Unit Size

Max Line Length

Max Elevation

(ID over OD)

Max Elevation

(OD over ID)

9 & 12K

65 (20)

35 (11)

35 (11)

18K

80 (25)

50 (15)

50 (15)

24K

100 (30)

50 (15)

50 (15)

S

The following are the piping sizes.

PIPE SIZES

Unit Size

Mix Phase

Vapor

9, 12 & 18K

1/4”

1/2”

24K

3/8”

5/8”

Refrigerant Charge

REFRIGERANT CHARGE

Unit Size

Amount of Charge lb. (kg)

9 K

2.65 (1.2)

12 K

2.8 (1.27)

18 K

3.5 (1.6)

24 K

5.4 (2.5)

S

Above charge is for piping runs up to 25 ft. (7.6 m).

S

For piping runs greater than 25 ft. (7.6 m), add 0.1 oz. of

refrigerant per foot of extra piping up to the allowable

length.

S

Capillary tubes are used as metering devices.

Connecting (Power and Control Cable)
S

The main power is supplied to the outdoor unit. The field

supplied connecting cable from the outdoor unit to indoor unit
consists of four wires and provides the power for the indoor unit
as well as the communication signal and ground between the

outdoor and indoor unit.
Two wires are high voltage AC power, one is low voltage and

one is a ground wire.

S

Consult local building codes, NEC (National Electrical Code) or

CEC (Canadian Electrical Code) for special requirements.

Model Size

Power Source

MIN CKT AMP

MAX FUSE/CB

AMP

9 K

115 --- 1 --- 60

20/25

12 K

115 --- 1 --- 60

20/25

12 K

208/230 --- 1 --- 60

10/15

18 K

208/230 --- 1 --- 60

14/25

24 K

208/230 --- 1 --- 60

16/30

S

Connecting Cable: Voltage drop on the connecting cable

should be kept to a minimum. Do not use thermostat wire. Use
cable size and max length below:

18 AWG

50 Feet (16 m)

16 AWG

65 Feet (19.8 m)

14 AWG

>65 Feet (19.8 m)

38/

40GX

C

(Q

)