TROUBLESHOOTING

This unit has onboard diagnostics. Error codes will appear on the LED display on the front panel of the indoor unit in place of the

temperature display. Error codes are also displayed on the outdoor unit microprocessor board with colored LED lights. The table below
explains the error codes for both units.

38GXC/GXQ -- 40GXC/GXQ 009--024 Diagnostic Codes

Equipment Fault

Code Displayed

on Indoor Unit

Front Panel

LED Display on Outdoor Unit Board

Possible Cause

Green

LED

Number

of Flashes

Red

LED

Number

of Flashes

Yellow

LED

Number

of Flashes

Freeze Protection, Indoor Coil

E2

4

3

Low Refrigerant Charge, Blocked Indoor Air

Flow, or Dirty Air Filter

High Compressor Discharge Temperature

E4

7

Low Refrigerant Charge, Blocked Capillary,

or High Ambient Temperature

Low Voltage Protection

E5

5

Low Voltage

Communication Error

E6

0

Wiring Error, or Communication Failure

Indoor Air Temperature Thermistor

F1

Bad Connection, or Sensor Failure

Indoor Coil Temperature Thermistor

F2

Bad Connection, or Sensor Failure

Outdoor Air Temperature Thermistor

F3

6

Bad Connection, or Sensor Failure

Outdoor Coil Temperature Thermistor

F4

5

Bad Connection, or Sensor Failure

Compressor Discharge Line Thermistor

F5

7

Bad Connection, or Sensor Failure

Defrost

H1

2

Unit going through normal defrost cycle

Compressor Overload Protection

H3

8

Low Refrigerant Charge, Blocked Capillary,

or Compressor Motor Failure

Compressor Over Current Protection

H4

6

High Ambient Temperature, or Loss of

Condenser Airflow

IPM Module Protection

H5

4

Loss of Cooling to Heat Sink, High Ambient,

Low Voltage, or Bad Connections

38/

40GX

C

(Q

)