Installation guide, Indoor unit installation, Install mounting plate – Carrier 40GXQ User Manual
Page 6: 38/ 40gx c (q )
6
INSTALLATION GUIDE
Ideal installation locations include:
Indoor Unit
S
A location where there are no obstacles near inlet and outlet area.
S
A location which can bear the weight of indoor unit.
S
Do not install indoor units near a direct source of heat such as
direct sunlight or a heating appliance.
S
A location which provides appropriate clearances as outlined in
Fig. 2 (pg. 5).
Outdoor Unit
S
A location which is convenient to installation and not exposed to
strong wind. If unit is exposed to strong winds it is
recommended that a wind baffle be used. Contact your Carrier
Representative for drawings. (See Fig. 11, pg. 7)
S
A location which can bear the weight of outdoor unit and where
the outdoor unit can be mounted in a level position.
S
A location which provides appropriate clearances as outlined in
Fig. 3 (pg. 5).
S
Do not install the indoor or outdoor units in a location with
special environmental conditions. For those applications, contact
your Carrier Representative.
INDOOR UNIT INSTALLATION
INSTALL MOUNTING PLATE
1. Carefully remove the mounting plate, which is attached to
the back of the indoor unit.
2. The mounting plate should be located horizontally and level
on the wall. All minimum spacings shown in Fig. 4
through Fig. 7 should be maintained.
3. If the wall is block, brick, concrete or similar material, drill
.2” (5 mm) diameter holes and insert anchors for the ap-
propriate mounting screws.
4. Attach the mounting plate to the wall.
.04 (1)
8.58 (218)
2.64 (67)
.08 (2)
4.09 (104)
.52 (13)
15.47 (393)
18.94 (481)
65
A085862
Fig. 4
--- 9k Mounting Plate Spacing
65
3.15 (80)
21.93 (557)
7" (178)
10.4 (264)
Note: Units in ( ) = mm
10.4 (264)
A08291
Fig. 5
--- 12k Mounting Plate Spacing
25.6 (650.5)
10.1 (256)
A09664
Fig. 6
--- 18k Mounting Plate Spacing
1
1
.4 (290)
A09665
Fig. 7
--- 24k Mounting Plate Spacing
DRILL HOLE IN WALL FOR INTERCONNECTING
PIPING, DRAIN AND WIRING
Refrigerant Line Routing
The refrigerant lines may be routed in any of the four directions
shown in Fig. 8 (a) and (b).
For maximum serviceability, it is recommended to have refrigerant
line flare connections and the drain connection on the outside of
the wall that the fan coil is mounted on.
1 Right Exit
2 Right Rear Exit
3
Left Exit
4
Left Rear Exit
( a )
( b )
( c )
As viewed from front
Knockout 3
Knockout 2
Knockout 1
A08281
Fig. 8
--- Refrigerant Line Routing
If piping is going through the back:
1. Determine pipe hole position using the mounting plate as a
template. Drill pipe hole diameter per chart below. The
outside pipe hole is 1/2--in. (13 mm) min. lower than inside
pipe hole, so it slants slightly downward (see Fig. 9).
If piping is going to exit from the left rear, it is recommen-
ded to field--fabricate piping extensions to get the flare con-
nections to the outside of the wall.
1/2 in. (13 mm)
Min.
INDOOR
OUTDOOR
A07371
Fig. 9
--- Drill Holes
Model Size
Hole Diameter
in. (mm)
9k, 12k and 18k
2.56 (65)
24k
3.75 (95)
38/
40GX
C
(Q
)