Specifications – Tycon Power TPDIN-Monitor-WEB User Manual
Page 6

6
State Of Charge Sealed or Flooded
Lead Acid
GEL Battery
AGM Battery
100%
12.7+Volts
12.9+Volts
12.8+Volts
75%
12.4 Volts
12.7 Volts
12.6 Volts
50%
12.2 Volts
12.4 Volts
12.3 Volts
25%
12.0 Volts
12.0 Volts
12.0 Volts
10%
11.8 Volts
11.8 Volts
11.8 Volts
Voltage Meas (DC)
V1, V2, V3, V4 = 1-80VDC
Voltage Meas Accuracy
+/- 0.1V
Current Meas (DC)
I1, I2 = 0.1A to 20A
I3, I4 = +/-10A
Current Meas Accuracy
+/- 0.1A
Temperature Meas
T1,T2 = -40C to 125C
Temp Meas Type
T1 = Embedded, T2 = External Sensor (included)
Temp Meas Accuracy
+/- 1 degC
Relays (Normally Closed
Type)
R1, R2, R3, R4 = 10A DC
Relay Control
R1, R2 = Manual or Ping or Time Control
R3, R4 = Manual or Temperature Control
Power Requirements
10-58VDC Wire Terminal or 802.3af Class 0 POE,
3W Typ
Accessibility
Via Web Browser and SNMP
Data-Logger
FIFO, Max 1300 data sets, Program log interval
Connections
Removable Wire Terminal
Wire Size
12AWG Max
Mounting
DIN Rail
Operating Temperature
-40C to +75C (-40F to 167F)
Humidity (RH)
0% - 90%
Dimensions (LxWxH)
125 x 102 x 46mm (4.9” x 4” x 1.8”)
Weight
410g (14.5 oz)
5. Operating Power: The TPDIN-Monitor-WEB has extremely low op-
erating power, typically less than 3W. The relays are normally closed
type so in typical operation they don’t take any power until they are en-
ergized. If the relays are turned on to hold them open, the power usage
will increase.
6. SNMP: The TPDIN-Monitor-WEB can be controlled via SNMP for
automated operation. Setup the SNMP on the SNMP page in the web
interface. The unit will respond to SNMP queries to gather data and
control relays from a script running on a remote computer. The unit
doesn’t allow setting of local SNMP traps.
Specifications