beautypg.com

Tycon Power TPDIN-Monitor-WEB User Manual

Page 3

background image

3

STEP 10:

Open the System Page. You should add meaningful labels to

all the Voltages, Currents, Relays and Temperatures that you are using.

You can also change various settings on this page.

Relays: Relays are normally closed to save power when “on”. If you

want them to be initially open at power-up, check the box that says

“Initial Off”.

Cycle Delay: This controls how long the relay stays in the opposite

state when cycle is clicked on the Monitor Screen.

Voltage, Current and Temp Offsets: You can enter + or –offset values

if you want to calibrate the TPDIN-Monitor-WEB to match another piece

of measurement equipment or compensate for cable losses.

Log Interval: This sets the number of seconds between log readings.

The log can store 1300 data sets. If this is exceeded the oldest records

will be discarded as new records are entered. Note: If set to 0 the log-

ging of data is disabled and the graphs and some other functions won’t

work.

Time: There is no real time clock so if the device loses power the clock

will reset. Enable NTP to get the time automatically from the internet.

Set GMT for your time zone. Or you can sync the clock manually to

your PC Time by disabling NTP.