Specifications – Tycon Power UPS-ST12-50 User Manual
Page 6
6
The UPS-ST24 and UPS-ST48 are rated at 192W load output.
3. VENTING: The enclosure is vented thru the wire feedthrus and vari-
ous hole plugs in the bottom of the enclosure. Don’t make these airtight
with silicon
4. BATTERY MAINTENANCE: The batteries used in the UPSPro sys-
tems don’t require any maintenance. They should last up to 5 years in
normal use. Note: Never store batteries for any length of time in a dis-
charged state or it will kill the battery.
5. BATTERY OVERDISCHARGE: We highly recommend hooking
all equipment loads to the controller voltage output. This output will dis-
connect the load if the battery voltage drops below the set voltage and
this will protect the battery from over-discharge. If batteries get com-
pletely discharged because the equipment was connected directly to
the battery, you will reduce the battery life. Discharged batteries will
freeze at very low temperatures.
SPECIFICATIONS
Subject to change without notice
UPS-ST12
UPS-ST24
UPS-ST48
Load Voltage
12V +/-0.5
24V +/- 0.5
48V +/- 0.5
Max Load
12A (144W)
8A (192W)
4A (192W)
Min Load
1A
1A
1A
Capacity
1 battery 51Ah
600VA
2 battery 102Ah
1200VA
4 battery 204Ah
2400VA
2 battery 51Ah
1200VA
4 battery 102Ah
2400VA
4 battery 51Ah
2400VA
Battery Type
Valve Regulated Sealed Lead Acid / GEL
Battery Life
5 Years
Charge Voltage
WET Equalize =
14.6V, Float =
13.2V
GEL Equalize =
14.2V, Float =
13.5V
WET Equalize =
28.8V, Float =
26.4V
GEL Equalize =
28.4V, Float =
27V
WET Equalize =
58V, Float = 53V
GEL Equalize =
56.8V, Float =
54V
Over-discharge
protection
10.7V Load Off
12.6V Load On
21.5V Load Off
25.2V Load On
40V Load Off
51V Load On
VAC +/- 10%
Selector Switch 120VAC / 240VAC , 50/60Hz
Input Current
3.5A @ 115VAC / 1.8A @ 240VAC
Enclosure Type
Powder Coat Steel
Operating
Temp
-30°C to +60°C