beautypg.com

Tjernlund XCOP1 Constant Operating Pressure Exhaust Control 8504175 (Discontinued) User Manual

Page 4

background image

3

The XCOP1 must be installed by a qualified installer (an
individual properly licensed and/or trained) in accordance
with all local codes or, in their absence, in accordance with
the National Electrical Code.

All wiring from the XCOP1 to the RT-Series Fan junction box
must be appropriate Class 1 wiring as follows: installed in
rigid metal conduit, intermediate metal conduit, rigid non-
metallic conduit, electrical metallic tubing, Type MI Cable,
Type MC Cable, or be otherwise suitably protected from
physical damage.

COP CONTROL POWER CONNECTIONS

Connect 115 VAC supply voltage to L & N terminals and
Ground wire to ground on COP control terminal block.
Important: Installer must supply overload and disconnect
protection. COP Control power may be switched through a
building management system, pressure switch or other 115
VAC switch.

RT-SERIES MOTOR & COOLING FAN CONNECTIONS

NOTE: The maximum distance wire can be ran from the
RT-Series Rooftop Fan 4 x 4 Junction box to the XCOP1
control is 250 feet.

Cut Orange motor capacitor wire in RT-Series fan provided
4 x 4 Junction box and cap end with a wire nut that previ-
ously went to RT-Series Inducer motor.

Connect the Orange Motor Capacitor lead to the MOTOR
ORG location on COP terminal strip.

Connect Red and White/Red motor leads from RT-Series
Fan whip to MOTOR RED and WHT/RED location on COP
terminal strip.

Connect the Black & White Cooling Fan leads to COOL FAN
WHT and BLK location on COP terminal strip.

4 FT. WHIP

PRE-WIRED

N.O.

COM

ORG

RED

WHT

BLK

1303284

WHT/

GRN

RED

PROVER

MOTOR

COOL FAN

P2

T1

1

P1

T7

N

GR

N

L

WH

T/R

E

D

YEL

OR

G

BL

U

RE

D

WH

T

BL

K

T1

4

BLK

WHT

GRN

L

N

1303285

T14

T11

T7

T10

WHITE / RED

ORG

RED

GROUND

INCLUDED

N

L1

COP

POWER SUPPLY

115 VAC

MOTOR

CAPACITOR

G

R

O

UND

WH

ITE

BL

AC

K

RE

D

BROWN

WH

ITE

/ R

E

D

COOLING FAN

THERMOSTAT

INDUCER

MOTOR

THERMOSTAT

WH

T / R

ED

BL

AC

K

BR

OW

N

OR

AN

GE

BR

OW

N

RE

D

NUT

S

OR

AN

GE

BL

AC

K

RE

D

WH

T / R

ED

WH

ITE

WH

ITE

BLUE

BLUE

BLACK

INCLUDED 4 X 4 BOX

IMPELLER

WI

RE

BLACK

ORANGE

ORANGE

SIDE VIEW

CUTAWAY

RT SERIES

WHITE

BLK

T9

T6

WIRING CONNECTIONS BETWEEN XCOP1 AND ROOFTOP RT-SERIES FAN

POWER SUPPLY

MAY BE SWITCHED