The drain pipe installation for the unit with pump.

The drain pipe installation for the unit without pump.

Lean over 1/50

200mm

/7.87in

550mm

/21.65in

1-1.5m

/3.28-4.92ft

Fig.11-1

Fig.11-2

Lean over 1/50

1-1.5m

/3.28-4.92ft

Drainage test

Drainage test

Check whether the drainpipe is unhindered.
New built house should have this test done before paving

the ceiling.

The unit with pump.

Remove the test cover, and stow about 2000ml water to the

water pan.

1

NOTE

Fig.11-5

Install the drain joint of the outdoor unit

(For Heat Pump Models)

Fit the seal into the drain joint, then insert the drain joint into the

base pan hole of outdoor, rotate 90° to securely assemble them.

Connect the drain joint with an extension drain hose (Locally

purchased)to avoid condensate draining off the outdoor unit

during the heating mode.

Seal

Base pan hole

Drain joint

Seal

Base pan

Drain

joint

Fig.11-6

All the figures in this manual are for explanation purpose only.

They may be slightly different from the air conditioner you

purchased.The actual unit shall prevail.

The unit without pump.

Stow 2000ml water to the water pan through the stow

tube,check whether the drainpipe is unhindered.

Stow tube

Fig.12-1

12. FRESH AIR DUCT INSTALLATION

Dimension :

Duct joint for fresh air

80mm/3.15in

80mm/3.15in

Ø90mm/3.54in

Ø125mm/4.92in

Ø160mm/6.3in

MODLE

12-24

30-60

Operate the air conditioner in "COOLING" mode. The sound of

the drain pump shall be heard. Check whether the water is

discharged well (1 min lag is possible, according to the length of

the drain pipe), and check whether the water leaks from the

joints.

2

Power off the air conditioner and recover the cap.

3

Test cap

Fig.11-3

Fig.11-4

CLOSED

O

PE

N

CL

OS

ED

OPEN

Stow tube