beautypg.com

5 moving and installation, Model b c – Pridiom Concealed Duct Installation Manual User Manual

Page 16

background image

installation manual

14

6.5 Moving and installation

Fig.6-15

>60cm /23.62in

Fix with bolt

Since the gravity center of the unit is not at its physical

center, so please be careful when lifting it with a sling.

Never hold the inlet of the outdoor unit to prevent it from

deforming.

Do not touch the fan with hands or other objects.

Do not lean it more than 45, and do not lay it sidelong.

Make concrete foundation accoding to the sepecif-ications of

the outdoor units.(Refer to Fig.6-15)

Fasten the feet of this unit with bolts firmly to prevent it from

collapsing in case of earthquake or strong wind.(Refer to

Fig.6-15)

1. Foundation could be on flat and is recommended be 100-300mm
/3.94-11.81in higher than ground level.
2.Install a drainage around foundation for smooth drain
3.When installing the outdoor unit fix the unit by anchor bolts of M10
4.When installing the unit on a roof or a veranda,

drain

water

sometimes turns to ice on the cold weather. Therefore, avoid
draining in an area that people often use because it is slippery.

Concrete Foundation

Fig.6-16

≥100

3.94in

10

0

30

0

3.94~1

1.81in

B

C

unit:mm

1. Suspend the unit as the drawing indicates.
2. Ensure that ceiling can resist the Outdoor unit weight indicated
in specification label plate.

Suspended unit

No

Description

Outdoor Unit

Vibration-proof rubber

Anchor Bolt M10

Drainage (Wide 100/3.94in×Depth 150/5.9in)

Drainage

Mortar Hole (Φ100/3.94in×Depth 150/5.9in)

Sling Bolt

Suspension Bracket

Table 6-4

Table 6-5

Fig.6-17

MODEL

B

C

1120/44.1in 720/28.35in

1338/52.67in 820/32.28in

1338/52.67in 820/32.28in

1338/52.67in 820/32.28in

18~24

30

36

48~60

1
2
3
4
5
6

Outfall

Fig.6-18

NOTE: Make sure 3-4 degree of angel is kept between the unit and

the floor when the unit is installed in the low temperauture

and humid environment.

Make sure the ice on the chassis of the outdoor unit can be

dealt with when the unit is installed in the low temperature

and humid enviroment.

The outdoor unit should be installed in mounting rack 30cm

/11.81in high.The enviroment temperature should be above

0°.