6.5 Moving and installation
Fig.6-15
>60cm /23.62in
Fix with bolt
Since the gravity center of the unit is not at its physical
center, so please be careful when lifting it with a sling.
Never hold the inlet of the outdoor unit to prevent it from
deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation accoding to the sepecif-ications of
the outdoor units.(Refer to Fig.6-15)
Fasten the feet of this unit with bolts firmly to prevent it from
collapsing in case of earthquake or strong wind.(Refer to
Fig.6-15)
1. Foundation could be on flat and is recommended be 100-300mm
/3.94-11.81in higher than ground level.
2.Install a drainage around foundation for smooth drain
3.When installing the outdoor unit fix the unit by anchor bolts of M10
4.When installing the unit on a roof or a veranda,
drain
water
sometimes turns to ice on the cold weather. Therefore, avoid
draining in an area that people often use because it is slippery.
Concrete Foundation
Fig.6-16
≥100
3.94in
10
0
~
30
0
3.94~1
1.81in
B
C
unit:mm
1. Suspend the unit as the drawing indicates.
2. Ensure that ceiling can resist the Outdoor unit weight indicated
in specification label plate.
Suspended unit
No
Description
Outdoor Unit
Vibration-proof rubber
Anchor Bolt M10
Drainage (Wide 100/3.94in×Depth 150/5.9in)
Drainage
Mortar Hole (Φ100/3.94in×Depth 150/5.9in)
Sling Bolt
Suspension Bracket
Table 6-4
Table 6-5
Fig.6-17
MODEL
B
C
1120/44.1in 720/28.35in
1338/52.67in 820/32.28in
1338/52.67in 820/32.28in
1338/52.67in 820/32.28in
18~24
30
36
48~60
1
2
3
4
5
6
Outfall
Fig.6-18
NOTE: Make sure 3-4 degree of angel is kept between the unit and
the floor when the unit is installed in the low temperauture
and humid environment.
Make sure the ice on the chassis of the outdoor unit can be
dealt with when the unit is installed in the low temperature
and humid enviroment.
The outdoor unit should be installed in mounting rack 30cm
/11.81in high.The enviroment temperature should be above
0°.
The machine must be installed indoor.