beautypg.com

Wiring instructions, Wiring diagrams, Wiring diagram - standard – Code 3 WingMan with TriCore for Crown Victoria User Manual

Page 6: Warning

background image

6

Wiring Diagrams

It is advisable to leave an extra loop of cable when installing the light bar to allow for future changes or reinstallations.

Connect the black lead to a solid frame ground (earth), preferably the (-) or ground (earth) side of the battery, and the

power wire to the +12V terminal of the battery. Connect the remaining wires as shown below. For light bars with the

ArrowStik® option see wiring diagram WITH ARROWSTIK on page 7.

Wiring Diagram - STANDARD

Larger wires and tight connections will provide longer service life for components. For high current wires it

is highly recommended that terminal blocks or soldered connections be used with shrink tubing to protect

the connections. Do not use insulation displacement connectors (e.g. 3M

®

Scotchlock type connectors).

Route wiring using grommets and sealant when passing through compartment walls. Minimize the

number of splices to reduce voltage drop. High ambient temperatures (e.g. under hood) will significantly

reduce the current carrying capacity of wires, fuses, and circuit breakers. Use "SXL" type wire in engine

compartment. All wiring should conform to the minimum wire size and other recommendations of the

manufacturer and be protected from moving parts and hot surfaces. Looms, grommets, cable ties, and

similar installation hardware should be used to anchor and protect all wiring. Fuses or circuit breakers

should be located as close to the power takeoff points as possible and properly sized to protect the wiring

and devices. Particular attention should be paid to the location and method of making electrical connections

and splices to protect these points from corrosion and loss of conductivity. Ground terminations should

only be made to substantial chassis components, preferably directly to the vehicle battery. The user should

install a fuse sized to approximately 125% of the maximum Amp capacity in the supply line to protect

against short circuits. For example, a 30 Amp fuse should carry a maximum of 24 Amps. DO NOT USE

1/4" DIAMETER GLASS FUSES AS THEY ARE NOT SUITABLE FOR CONTINUOUS DUTY IN SIZES

ABOVE 15 AMPS. Circuit breakers are very sensitive to high temperatures and will "false trip" when

mounted in hot environments or operated close to their capacity.

WARNING!

Wiring Instructions

FUSE WITH CUSTOMER SUPPLIED 10 AMP FUSE

GREEN (PATTERN SELECT)

WHITE (DIMMING)

RED (POWER)

YELLOW (LEVEL 3)

ORANGE (LEVEL 2)

BLUE (LEVEL 1)

BLACK (GND)