beautypg.com

Electrical data, Electrical data -28 – Carrier 30XW325-400 User Manual

Page 26

background image

26

STANDARD SINGLE INPUT POWER CONFIGURATION

LEGEND

NOTES:

1. Each main power source must be supplied from a field-supplied fused

electrical service with a (factory-installed or field-installed) disconnect
located in sight from the unit.

2. Control circuit power must be supplied from a separate source through

a field-supplied disconnect. An optional control transformer may be
used to provide control circuit power from the main unit power supply.

3. Maximum instantaneous current flow (ICF) during start-up is the point

in the starting sequence where the sum of the LRA for the start-up
compressor, plus the total RLA for all running compressors is at a
maximum.

4. Maximum incoming wire size for each terminal block is 500 kcmil.
5. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
6. Use copper conductors only.
7. The MOCP is calculated as follows:

MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the
fuse one size down from the result. The RLAs are listed on the
nameplate.

The recommended fuse size in amps (RFA) is calculated as follows:
RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse
one size up from the result. The RLAs are listed on the nameplate.

30XW

UNIT

SIZE

UNIT VOLTAGE

NO. POWER

SUPPLY

CONDUCTORS

MCA

MOCP

ICF

REC FUSE

SIZE

CONTROL CIRCUIT

V-Ph-Hz

Supplied

V-Ph-Hz

MCA and

MOCP

Min

Max

WD

XL

325

200-3-60

187

220

9

920.3

1200

1347.0

1200

115-1-60

20

230-3-60

207

253

9

799.0

1000

1171.1

1000

115-1-60

20

380-3-60

342

418

6

487.6

700

710.7

1753.7

600

115-1-60

20

460-3-60

414

506

6

401.0

500

586.2

1448.2

450

115-1-60

20

575-3-60

518

633

3

317.3

450

467.0

1157.0

400

115-1-60

20

325

HM

200-3-60

187

220

12

1168.2

1600

1848.2

1600

115-1-60

20

230-3-60

207

253

9

1018.4

1200

1608.6

1200

115-1-60

20

380-3-60

342

418

6

614.5

800

973.1

2452.1

700

115-1-60

20

460-3-60

414

506

6

510.8

700

805.0

2027.0

600

115-1-60

20

575-3-60

518

633

6

406.8

500

642.8

1620.8

450

115-1-60

20

350

200-3-60

187

220

9

920.3

1200

1347.0

1200

115-1-60

20

230-3-60

207

253

9

799.0

1000

1171.1

1000

115-1-60

20

380-3-60

342

418

6

487.6

700

710.7

1753.7

600

115-1-60

20

460-3-60

414

506

6

401.0

500

586.2

1448.2

450

115-1-60

20

575-3-60

518

633

3

317.3

450

467.0

1157.0

400

115-1-60

20

350

HM

200-3-60

187

220

12

1168.2

1600

1848.2

1600

115-1-60

20

230-3-60

207

253

9

1018.4

1200

1608.6

1200

115-1-60

20

380-3-60

342

418

6

614.5

800

973.1

2452.1

700

115-1-60

20

460-3-60

414

506

6

510.8

700

805.0

2027.0

600

115-1-60

20

575-3-60

518

633

6

406.8

500

642.8

1610.8

450

115-1-60

20

400

200-3-60

187

220

9

1041.3

1200

1400.8

1200

115-1-60

20

230-3-60

207

253

9

902.9

1200

1217.3

1200

115-1-60

20

380-3-60

342

418

6

545.2

700

736.3

1779.3

700

115-1-60

20

460-3-60

414

506

6

452.9

600

609.3

1471.3

600

115-1-60

20

575-3-60

518

633

3

366.3

500

488.8

1178.6

450

115-1-60

20

400

HM

200-3-60

187

220

12

1329.8

1600

1920.0

1600

115-1-60

20

230-3-60

207

253

12

1156.7

1600

1670.1

1600

115-1-60

20

380-3-60

342

418

6

700.9

1000

1011.5

2490.5

800

115-1-60

20

460-3-60

414

506

6

579.8

800

835.7

2057.7

700

115-1-60

20

575-3-60

518

633

6

464.4

600

668.4

1646.4

600

115-1-60

20

ICF

Maximum Instantaneous Current Flow

HM

Heat Machine Units

LRA

Locked Rotor Amps

MCA

Minimum Circuit Ampacity (for wire sizing)

MOCP — Maximum Overcurrent Protection
RLA

Rated Load Amps

WD

Wye-Delta Start

XL

Across-the-Line Start

Electrical data