REQ’D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 36 (914)

Compressor access

. . . . . . . . . . . . . . . . . . . . . 36 (914)

(Except for NEC requirements)

REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 14 (356)

Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel

. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

NEC REQ’D CLEARANCES. in. (mm)

Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)

UNIT

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

CORNER WEIGHT

(lb/kg)

lb

kg

A

B

C

D

48SX024040

208/230-1-60

333

151

104/47

50/23

130/59

49/22

48SX024060

208/230-1-60

345

157

107/49

53/24

133/60

52/24

48SX030040

208/230-1-60

336

153

97/44

66/30

118/54

55/25

48SX030060/080

208/230-1-60

348

158

100/45

69/31

121/55

58/26

48SX036060/080

208/230-1-60, 208/230-3-60, 460-3-60

366

166

94/43

84/38

117/53

71/32

48SX036100/120

208/230-1-60, 208/230-3-60, 460-3-60

378

172

97/44

87/40

120/55

74/34

UNIT

CENTER OF GRAVITY (in./mm)

X

Y

Z

48SX024040

26.71/678

20.06/510

12.65/321

48SX024060

26.64/677

20.12/511

12.65/321

48SX030040

27.06/687

21.05/535

12.65/321

48SX030060/080

26.98/685

21.07/535

12.65/321

48SX036060/080

27.14/689

21.10/536

12.65/321

48SX036100/120

27.06/687

21.12/536

12.65/321

LEGEND

CG

Center of Gravity

COND — Condenser
LV

Low Voltage

MAT’L

Material

NEC

National Electrical Code

REQ’D — Required

NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-

fan discharge.

2. Adequate clearance around air openings into combustion chamber must

be provided.

Fig. 6 — 48SX024-036 Without Base Rail, Unit Dimensions