Table 14 — Dry-Coil Air Delivery* — Downflow Discharge at 230 and 460 V — Unit 48SX

(Deduct 10% from Cfm and Watts for 208 V Operation)

UNIT

48SX

MOTOR

SPEED

AIR

DELIVERY

EXTERNAL STATIC PRESSURE (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

024,
030

Low

Watts

280

275

265

255

250

245

240

Cfm

820

810

755

700

660

600

560

Med

Watts

365

360

350

345

340

330

320

310

300

Cfm

1025

1010

975

940

900

850

800

720

630

High

Watts

490

480

470

460

445

430

410

390

380

Cfm

1300

1255

1200

1150

1080

1005

915

790

620

036

Low

Watts

520

495

474

458

445

425

Cfm

1375

1335

1290

1240

1200

1140

Med

Watts

575

560

535

510

480

460

440

425

Cfm

1520

1490

1450

1400

1380

1300

1200

1080

High

Watts

650

614

575

540

510

480

Cfm

1560

1500

1380

1280

1170

1060

042

Low

Watts

490

480

470

460

450

430

410

390

Cfm

1400

1380

1340

1300

1250

1200

1140

1070

Med

Watts

590

580

560

545

525

505

480

450

420

Cfm

1600

1560

1540

1470

1430

1360

1300

1220

1120

High

Watts

700

670

640

600

560

500

Cfm

1780

1670

1600

1480

1340

1100

048**

Low

Watts

1050

1000

970

930

870

810

750

680

600

Cfm

1850

1830

1800

1785

1750

1700

1640

1500

1330

High

Watts

1050

1000

930

870

810

740

665

Cfm

2000

1940

1850

1750

1635

1500

1300

*Air delivery values are without air filter and are for dry coil. See Table 17

for wet coil pressure drop. Deduct field-supplied air filter pressure drop
and wet coil pressure drop to obtain external static pressure available
for ducting.

†Unit air delivery is outside of operating range.

**For 460 v units only.

NOTE: Do not operate the unit at a cooling airflow that is less than
350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-coil
icing may occur at airflows below this point. Water blow-off may occur at
airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.

Table 15 — Dry Coil Air Delivery* — Heating —

Horizontal and Downflow Discharge for Integrated
Control Motor Units at 230-V (Deduct 10% from Cfm

for 208-V Operation)

HEATING

INPUT
(Btuh)

EASY SELECT BOARD TERMINALS (Cfm)

1

2

3

4

80,000

1300

1400

1600

1750

100,000

1400

1600

1750

95,000

1600

1750

136,000

1750

*Air delivery values are for dry coil at 230 v. Airflow is independent of

external static pressure within

Ϯ

5% of table values up to

0.8 in wg.

NOTES:
1. Dashed areas do not fall within approved range.
2. The above values occur with the AC/HP CFM ADJUST select jumper

set on MED.

3. Airflow can be adjusted

ϩ

10% or −10% by selecting HI or LO for

all modes except FAN ONLY.

Table 16 — Dry-Coil Air Delivery* — Fan Only and
Cooling — Horizontal and Downflow Discharge for
Integrated Control Motor Units at 230-V (Deduct 10%

from Cfm for 208-V Operation)

UNIT 48SX

FAN ONLY (Cfm)

COOLING (Cfm)

048

1400

1600

060

1750

2000

*Air delivery values are for dry coil at 230 v. Airflow is independent of

external static pressure within

Ϯ

5% of table values up to

0.8 in wg.

NOTE: Do not operate the unit at a cooling airflow that is less than
350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-
coil icing may occur at airflows below this point. Water blow-off may
occur at airflows above 450 cfm per 12,000 Btuh of rated cooling
capacity.