Cisco ASR 1004 User Manual
Page 34
34
Figure 14
Cisco ASR 1004 Router DC Power Supply Terminal Block
Step 8
Tighten the Kepnut screw (use the screwdriver to tighten the ground screw in the terminal block to a torque of 8 in-lbs
/ 4 per.) and repeat the same steps for the positive ground stud and wire.
Note
Secure the wires coming in from the terminal block so that they cannot be disturbed by casual contact.
Step 9
Use tie wraps to secure the wires, so that the wires are not pulled from the terminal block by casual contact. Ti-wrap
studs are located below the power supply terminal block.
Step 10
Replace the terminal block plastic cover, which slides over the terminal block; then tighten the screws (tighten the screw
to a torque of 5 in-lbs / 1 per.).
1
Ground lug and positive lead wire
4
Washer
2
Terminal block and positive stud
5
Kepnut screw
3
Earth grounding symbol