Problem solving, Troubleshooting – Crestron electronic infiNET EX CEN-RFGWX-EX User Manual

Page 29

background image

Crestron CEN-RFGW-EX

infiNET EX™ Gateway

Problem Solving

Troubleshooting

The following table provides corrective action for possible trouble
situations. If further assistance is required, please contact a Crestron
customer service representative.

CEN-RFGW-EX Troubleshooting

TROUBLE

POSSIBLE

CAUSE(S)

CORRECTIVE

ACTION

PWR LED does
not illuminate.

CEN-RFGW-EX is
not receiving
sufficient Cresnet
power.

Use the Crestron
Power Calculator to
help calculate how
much power is needed
for the system.

CEN-RFGW-EX is
not receiving
sufficient Ethernet
power.

Verify that appropriate
Ethernet power
sourcing equipment
(PSE) Power over
Ethernet indicator is
ON.

NET LED does
not illuminate.

CEN-RFGW-EX
Net ID is not set to
match the Net ID
of the SIMPL
program.

In Crestron Toolbox,
check Functions |
CresnetID
to verify
Net ID. Verify Net ID in
SIMPL Windows
program.

CEN-RFGW-EX is
not communicating
with network.

Check network cabling
for solid connections
and correct pinouts.

NET LED is on
but unit does
not
communicate
with infiNET EX
device.

CEN-RFGW-EX
Net ID is not
unique; two or
more units share
the same Net ID.

Verify the Net IDs for
all network devices are
unique when multiple
devices are used.

(Continued on following page)

Operations & Installation Guide – DOC. 6706A

infiNET EX™ Gateway: CEN-RFGW-EX