Installation

|

Hardwiring the UPS Input

WARNING:

Only qualified service personnel (such as a licensed electrician) shall perform the electrical

installation. Risk of electrical shock.

The Dell Line-Interactive Rack hardwired models require a dedicated branch circuit that meets the
following requirements:

S

5600W/208V models only:

40A 2-pole circuit breaker to provide short circuit and overcurrent

protection

S

5600W/230V models only:

32A for Europe (or 35A for North America) 2-pole circuit breaker to

provide short circuit and overcurrent protection

S

The protection device requires a two-pole disconnection device between the UPS output and the
load (see Figure 17)

S

The breaker must be wall-mounted and be readily accessible to the operator

S

For Europe, the breaker must meet the IEC/EN 60934 standard and have a contact air gap of at
least 3 mm

S

200–240 Vac

S

Single-phase

-

5600W/208V model is phase-to-phase (can also be used on a split-phase 120/240 Vac input)

-

5600W/230V model is phase-to-neutral

S

50/60 Hz

S

Flexible metal conduit (recommended for ease of service and maintenance)

AC Mains

Wall

2-Pole

Breaker

UPS

Line

Neutral

Figure 17. Circuit Breaker Diagram