WIRING

For applicable wiring diagram see Table 1

GROUND FAULT
MONITOR

TOGGLE SWITCH

SEE NOTES

ATTACHED TO
AUXILLARY TERMINALS

NOTES:
1. USE 90 DEG. C. MIN. WIRING.
2. USE COPPER CONDUCTORS ONLY.
3. VERIFY THAT VOLTAGE OF "STAR-TG"
MATCHES VOLTAGE OF HEATER.

BLACK

TRANSFORMER

WHITE

TO TERMINALS
INSIDE HEATER
JUNCTION BOX

POWER LEADS MUST
PASS THROUGH CURRENT
TRANSFORMER POSITION
OF GROUND FAULT
MONITOR

PRI. SIDE TRANSFORMER CONNECTION:
208V = BLK AND RED
240V = BLK AND ORG
277V = BLK AND BRN
380V = BLK AND VIOLET
480V = BLK AND BLK/RED
600V = BLK AND GRAY
UNUSED LEADS CAPPED OFF.

SUPPLY

CONTACTOR

CO

NC

NO

L2

L3

L1

1

3

2

G

L3
L2

GROUND FAULT
MONITOR

TOGGLE

SWITCH

TIPOVER

SWITCH

TIPOVER

SWITCH

CONTACTOR

SEE NOTES

ATTACHED TO
AUXILLARY
TERMINALS

NOTES:
1. USE 90 DEG. C. MIN. WIRING.
2. USE COPPER CONDUCTORS ONLY.
3. VERIFY THAT VOLTAGE OF "STAR-TG"
MATCHES VOLTAGE OF HEATER.

BLACK

TRANSFORMER

WHITE

TO TERMINALS
INSIDE HEATER
JUNCTION BOX

POWER LEADS MUST
PASS THROUGH CURRENT
TRANSFORMER POSITION
OF GROUND FAULT
MONITOR

PRI. SIDE TRANSFORMER CONNECTION:
208V = BLK AND RED
240V = BLK AND ORG
277V = BLK AND BRN
480V = BLK AND BLK/RED
380V = BLK AND VIOLET
600V = BLK AND GRAY
UNUSED LEADS CAPPED OFF.

SUPPLY

CO

NC

NO

3

2

1

L1

TOGGLE
SWITCH

TIPOVER
SWITCH

TIPOVER
SWITCH

CONTACTOR

TRANSFORMER

BLACK

WHITE

TO TERMINALS
INSIDE HEATER
JUNCTION BOX

NOTES:
1. USE 90 DEG. C. MIN. WIRING.
2. USE COPPER CONDUCTORS ONLY.
3. VERIFY THAT VOLTAGE OF "STAR-TIP"
MATCHES VOLTAGE OF HEATER.

PRI. SIDE TRANSFORMER CONNECTION:
208V = BLK AND RED
240V = BLK AND ORG
277V = BLK AND BRN
380V = BLK AND VIOLET
480V = BLK AND BLK/RED
600V = BLK AND GRAY
UNUSED LEADS CAPPED OFF.

3

L3
L2
L1

2
1

1

2

4

3

6

5

DISCONNECT

SWITCH

TERMINAL BLOCK

NOTES:
1. USE 90 DEG. C. MIN. WIRING.
2. USE COPPER CONDUCTORS ONLY.
3. TO MAINTAIN THE ENVIRONMENTAL
RATING OF THIS ENCLOSURE, USE
ONLY UL LISTED OR RECOGNIZED
LIQUID TIGHT CONDUIT HUBS.

TO TERMINALS
INSIDE HEATER
JUNCTION BOX

3

2

1

GRN L1

L2

L3

Fig. 1

Fig. 2

Fig. 3

Fig. 4