MAINTENANCE

The Chromalox STAR-TG tip over cutout with ground fault

sensor provides a reliable and cost effective method for sensing
ground faults and to shut off the heater in case of tip-over. The pur-
pose of the ground fault control is to monitor for ground faults,
sense potential heater failure symptoms and to protect equipment.

The current-carrying wires are routed through the current

transformer on the control. When ground current reaches the level
set by the trip point adjustment, (.03 amps), the relay trips, illumi-
nates the tripped LED and provides an output signal which de-
energizes the magnetic contactor.

ELECTRIC SHOCK HAZARD. Disconnect all power
to heater before installing or servicing kit(s).

Failure to do so could result in personal injury or
property damage. Kit(s) must be installed by a
qualified person in accordance with the National
Electrical Code, NFPA 70.

If heating element(s) fail to operate:

1. Open door of enclosure. DANGER: Hazard of Electric

Shock.

2. If "Tripped" indicator is not on, check for blown fuses or failed

electrical components in the heater’s electrical system includ-
ing the tip over trip mechanism.then this indicates one or more
heating elements are about to fail.

3. Check pendulums on the tip over switch mechanisms to be sure

they are not blocked.

4. If the "Tripped" indicator is on, then this indicates one or more

heating elements are about to fail. Disconnect power and fol-
low the GF Troubleshooting Diagram below.

Tripped Indicator

Light is On

Is this the

initial

installation?

Is this the first

time heater is

used for the

season?

Is the set point of
the GF sensor set
at a value less than
.03 amps?

Did the problem
occur after
working properly
during part of this
heating season?

This condition indicates
at least one element is
about to fail.

Call Chromalox
Service Dept.
1 800-368-2493

Close cover.

Does the

heater

operate?

Does the heater

operate?

1. Replace all elements.
2. Flip toggle switch back
and forth, one time to
reset GF sensor.

Do you want to

reduce future

down time and

maintenance

costs?

1. Turn set point dial
clockwise to .03 amps.
2. Flip toggle switch mounted ontop
of enclosure back and forth one
time, (this resets the GF sensor).

Unbuss wiring, check insulation resistance
on each element.
1. Each element to have at least 10 Meg
terminal to sheath.
2. If element does not have at least 10 Meg.
dry out element by applying half of the
rated voltage for one hour.
3. Rebuss elements, re-energize heater, flip
toggle switch back and forth, one time
to reset GF sensor.

Does the heater

operate?

Call Chromalox
Service Dept.
1 800-368-2493

Does the

heater

operate?

Close all covers.

Unbuss wiring, check insulation resistance
on each element.
1. Each element to have at least 10 Meg
terminal to sheath.
2. If element does not have at least 10 Meg.
dry out element by applying half of the
rated voltage for one hour.
3. Rebuss elements, re-energize heater, flip
toggle switch back and forth, one time
to reset GF sensor.

START

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

Close all covers.

Close all covers.

TG TROUBLESHOOTING DIAGRAM