Carrier SINGLE PACKAGED ELECTRIC COOLING UNITS 50GX User Manual

Page 4

background image

2. Place each of the four (4) metal lifting brackets into the

rigging holds in the composite pan.

3. Tighten the ratchet strap unit tight. Lifting brackets should be

secure in the rigging holds.

4. Attach the clevis or hook of sufficient strength to hole in the

lifting bracket (See Fig. 6).

5. Attach safety straps directly to the field supplied rigging straps

or clevis clip. Do not attach the safety straps to the lifting
brackets.

6. Use the top of the unit as a spreader bar to prevent the rigging

straps from damaging the unit. If the wood top is not available,
use a spreader bar of sufficient length to not damage the unit.

Fig. 3— 50GS048–060 and 50GX042–060 Unit Dimensions

UNIT

ELECTRICAL CHARACTERISTICS

UNIT WEIGHT

UNIT HEIGHT

IN. (MM)

”A”

CENTER OF GRAVITY

IN. (MM)

lb.

kg

X

Y

Z

50GS048

208/230-1-60, 208/230-3-60, 460-3-60

324

145

38.98 (990.2)

20.0 (508.0)

17.0 (432.0)

17.0 (432.0)

50GS060

208/230-1-60, 208/230-3-60, 460-3-60

389

176

38.98 (990.2)

19.0 (482.6)

16.0 (406.0)

17.0 (432.0)

50GX042

208/230-1-60, 208/230-3-60, 460-3-60

321

146

38.98 (990.2)

20.5 (520.7)

16.75 (425.5)

16.6 (421.6)

50GX048

208/230-1-60, 208/230-3-60, 460-3-60

326

148

38.98 (990.2)

19.5 (495.3)

17.6 (447.6)

18.0 (457.2)

50GX060

208/230-1-60, 208/230-3-60, 460-3-60

399

181

42.98 (1091.1)

20.5 (520.7)

16.2 (412.8)

17.6 (447.0)

C99006

REQUIRED CLEARANCE FOR OPERATION AND SERVICING

INCHES [mm]

EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]

POWER ENTRY SIDE....................................................................36.00 [914.0]

(EXCEPT FOR NEC REQUIREMENTS)

UNIT TOP .......................................................................................48.00 [1219.2]

SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]

DUCT PANEL .................................................................................12.00 [304.8] *

*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM

WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.

INCHES [mm]

TOP OF UNIT...................................................................................14.00 [355.6]

DUCT SIDE OF UNIT.........................................................................2.00 [50.8]

SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]

BOTTOM OF UNIT .............................................................................0.50 [12.7]

ELECTRIC HEAT PANEL .................................................................36.00 [914.4]

NEC. REQUIRED CLEARANCES.

INCHES [mm]

BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]

UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]

UNIT AND BLOCK OR CONCRETE WALLS AND OTHER

GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]

4