inspected at least once each year by a qualified service person. To
troubleshoot heating or cooling of units, refer to tables at the back
of the book.
The following are 50GS Cooling Charging Charts:
The following are 50GX Cooling Charging Charts:
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.

Table 8—Wet Coil Air Delivery (Deduct 10 percent for 208v)*

Horizontal and Downflow Discharge

Unit 50GS018-060

230 AND 460 VOLT

Unit

Motor

Speed

External Static Pressure (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

018

Low

Watts

227

212

196

177

165

153

-

-

-

-

-

Cfm

1000

915

825

710

530

340

-

-

-

-

-

Med

Watts

-

-

-

-

-

-

-

-

-

-

-

Cfm

-

-

-

-

-

-

-

-

-

-

-

High

Watts

287

275

266

253

242

234

226

-

-

-

-

Cfm

1150

1032

963

807

698

503

250

-

-

-

-

024

Low

Watts

280

275

270

267

264

262

260

-

-

-

-

Cfm

880

825

765

693

600

450

281

-

-

-

-

Med

Watts

380

375

365

360

355

350

344

335

312

-

-

Cfm

1136

1085

1010

946

865

787

650

495

360

-

-

High

Watts

485

475

470

460

455

445

437

430

415

385

-

Cfm

1415

1332

1266

1180

1100

1000

900

780

480

256

-

030

Low

Watts

280

275

270

267

264

262

260

-

-

-

-

Cfm

880

825

765

693

600

450

281

-

-

-

-

Med

Watts

380

375

365

360

355

350

344

335

312

-

-

Cfm

1136

1085

1010

946

865

787

650

495

360

-

-

High

Watts

485

475

470

460

455

445

437

430

415

385

-

Cfm

1415

1332

1266

1180

1100

1000

900

780

480

256

-

036

Low

Watts

-

470

458

445

430

415

399

384

-

-

-

Cfm

-

1352

1257

1240

1199

1107

1015

924

-

-

-

Med

Watts

-

-

514

501

487

471

455

438

422

-

-

Cfm

-

-

1338

1295

1288

1181

1111

968

813

-

-

High

Watts

-

-

-

646

636

626

614

602

589

-

-

Cfm

-

-

-

1385

1268

1196

1159

1032

948

-

-

042

Low

Watts

-

675

660

650

640

630

620

610

595

580

-

Cfm

-

1387

1326

1275

1204

1142

1081

995

918

850

-

Med

Watts

-

886

855

825

795

778

765

750

735

718

700

Cfm

-

1458

1406

1350

1285

1224

1163

1091

1013

932

870

High

Watts

-

-

-

1000

950

925

910

890

875

855

833

Cfm

-

-

-

1488

1424

1360

1296

1233

1148

1071

1005

048

Low

Watts

-

727

712

700

688

666

644

622

595

569

-

Cfm

-

1640

1600

1575

1505

1450

1390

1300

1205

1145

-

Med

Watts

-

853

836

821

807

782

756

730

699

667

640

Cfm

-

1860

1830

1770

1700

1642

1565

1482

1385

1290

1210

High

Watts

-

979

959

943

927

897

868

838

802

766

730

Cfm

-

2090

2048

1997

1922

1845

1750

1600

1550

1425

1380

060

Low

Watts

1033

949

864

836

822

808

772

737

705

674

642

Cfm

2050

2000

1945

1905

1880

1820

1775

1695

1627

1530

1480

Med

Watts

1084

1054

1024

994

971

955

928

897

867

835

803

Cfm

2248

2179

2110

2058

2000

1932

1885

1829

1740

1638

1569

High

Watts

-

-

1184

1152

1120

1102

1084

1056

1029

997

965

Cfm

-

-

2278

2207

2124

2041

2000

1960

1856

1748

1645

* Air delivery values are based on operating voltage of 230v or 460v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain

static pressure available for ducting.
NOTES:

1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below

this point.

2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.

19