Carrier SINGLE PACKAGED ELECTRIC COOLING UNITS 50GX User Manual
Page 19

inspected at least once each year by a qualified service person. To
troubleshoot heating or cooling of units, refer to tables at the back
of the book.
The following are 50GS Cooling Charging Charts:
The following are 50GX Cooling Charging Charts:
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
Table 8—Wet Coil Air Delivery (Deduct 10 percent for 208v)*
Horizontal and Downflow Discharge
Unit 50GS018-060
230 AND 460 VOLT
Unit
Motor
Speed
External Static Pressure (in. wg)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
018
Low
Watts
227
212
196
177
165
153
-
-
-
-
-
Cfm
1000
915
825
710
530
340
-
-
-
-
-
Med
Watts
-
-
-
-
-
-
-
-
-
-
-
Cfm
-
-
-
-
-
-
-
-
-
-
-
High
Watts
287
275
266
253
242
234
226
-
-
-
-
Cfm
1150
1032
963
807
698
503
250
-
-
-
-
024
Low
Watts
280
275
270
267
264
262
260
-
-
-
-
Cfm
880
825
765
693
600
450
281
-
-
-
-
Med
Watts
380
375
365
360
355
350
344
335
312
-
-
Cfm
1136
1085
1010
946
865
787
650
495
360
-
-
High
Watts
485
475
470
460
455
445
437
430
415
385
-
Cfm
1415
1332
1266
1180
1100
1000
900
780
480
256
-
030
Low
Watts
280
275
270
267
264
262
260
-
-
-
-
Cfm
880
825
765
693
600
450
281
-
-
-
-
Med
Watts
380
375
365
360
355
350
344
335
312
-
-
Cfm
1136
1085
1010
946
865
787
650
495
360
-
-
High
Watts
485
475
470
460
455
445
437
430
415
385
-
Cfm
1415
1332
1266
1180
1100
1000
900
780
480
256
-
036
Low
Watts
-
470
458
445
430
415
399
384
-
-
-
Cfm
-
1352
1257
1240
1199
1107
1015
924
-
-
-
Med
Watts
-
-
514
501
487
471
455
438
422
-
-
Cfm
-
-
1338
1295
1288
1181
1111
968
813
-
-
High
Watts
-
-
-
646
636
626
614
602
589
-
-
Cfm
-
-
-
1385
1268
1196
1159
1032
948
-
-
042
Low
Watts
-
675
660
650
640
630
620
610
595
580
-
Cfm
-
1387
1326
1275
1204
1142
1081
995
918
850
-
Med
Watts
-
886
855
825
795
778
765
750
735
718
700
Cfm
-
1458
1406
1350
1285
1224
1163
1091
1013
932
870
High
Watts
-
-
-
1000
950
925
910
890
875
855
833
Cfm
-
-
-
1488
1424
1360
1296
1233
1148
1071
1005
048
Low
Watts
-
727
712
700
688
666
644
622
595
569
-
Cfm
-
1640
1600
1575
1505
1450
1390
1300
1205
1145
-
Med
Watts
-
853
836
821
807
782
756
730
699
667
640
Cfm
-
1860
1830
1770
1700
1642
1565
1482
1385
1290
1210
High
Watts
-
979
959
943
927
897
868
838
802
766
730
Cfm
-
2090
2048
1997
1922
1845
1750
1600
1550
1425
1380
060
Low
Watts
1033
949
864
836
822
808
772
737
705
674
642
Cfm
2050
2000
1945
1905
1880
1820
1775
1695
1627
1530
1480
Med
Watts
1084
1054
1024
994
971
955
928
897
867
835
803
Cfm
2248
2179
2110
2058
2000
1932
1885
1829
1740
1638
1569
High
Watts
-
-
1184
1152
1120
1102
1084
1056
1029
997
965
Cfm
-
-
2278
2207
2124
2041
2000
1960
1856
1748
1645
* Air delivery values are based on operating voltage of 230v or 460v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
19