The ability to properly perform maintenance on this equip-
ment requires certain expertise, mechanical skills, tools, and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment other than those
procedures recommended in the User’s Manual. FAILURE
TO HEED THIS WARNING COULD RESULT IN SERI-
OUS PERSONAL INJURY AND POSSIBLE DAMAGE TO
THIS EQUIPMENT.

Failure to follow these warnings could result in serious
personal injury:
1. Turn off electrical power to the unit and install lockout tag

before performing any maintenance or service on the unit.

2. Use extreme caution when removing panels and parts. As

with any mechanical equipment, personal injury can result
from sharp edges, etc.

3. Never place anything combustible either on, or in contact

with, the unit.

Table 9—Wet Coil Air Delivery (Deduct 10 percent for 208v)*

Horizontal and Downflow Discharge

Unit 50GX024-060

230 AND 460 VOLT

Unit

Motor

Speed

External Static Pressure (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

024

Low

Watts

281

282

281

278

276

-

-

-

-

-

-

Cfm

833

776

702

638

554

Med

Watts

-

-

-

375

370

363

357

352

-

-

-

Cfm

-

-

-

894

800

754

636

518

-

-

-

High

Watts

-

-

-

-

-

468

457

444

431

423

-

Cfm

-

-

-

-

-

884

802

697

467

397

-

030

Low

Watts

246

244

243

241

-

-

-

-

-

-

-

Cfm

910

806

749

680

-

-

-

-

-

-

-

Med

Watts

343

339

336

332

328

322

317

-

-

-

-

Cfm

1148

1104

1028

958

850

782

645

-

-

-

-

High

Watts

-

-

-

-

441

432

421

410

400

-

-

Cfm

-

-

-

-

1102

988

896

783

529

-

-

036

Low

Watts

-

470

458

445

430

415

399

384

-

-

-

Cfm

-

1352

1257

1240

1199

1107

1015

924

-

-

-

Med

Watts

-

-

514

501

487

471

455

438

422

-

-

Cfm

-

-

1338

1295

1288

1181

1111

968

813

-

-

High

Watts

-

-

-

646

636

626

614

602

589

-

-

Cfm

-

-

-

1385

1268

1196

1159

1032

948

-

-

042

Low

Watts

-

625

614

605

593

574

549

518

485

454

-

Cfm

-

1540

1510

1473

1396

1348

1288

1192

1124

1037

-

Med

Watts

-

-

-

-

726

695

661

625

591

561

540

Cfm

-

-

-

-

1648

1593

1530

1446

1352

1237

1114

High

Watts

-

-

-

-

-

-

-

790

766

7421

713

Cfm

-

-

-

-

-

-

-

1616

1492

1394

1283

048

Low

Watts

-

588

577

572

566

556

539

517

491

-

-

Cfm

-

1514

1543

1467

1408

1374

1324

1237

1161

-

-

Med

Watts

-

756

738

719

699

676

650

623

596

572

555

Cfm

-

1785

1765

1706

1628

1577

1503

1421

1357

1298

1253

High

Watts

-

-

-

-

896

862

829

800

775

752

728

Cfm

-

-

-

-

1880

1804

1704

1547

1565

1406

1367

060

Low

Watts

903

898

873

842

814

792

777

764

743

701

618

Cfm

2190

2158

2081

2026

1958

1866

1822

1744

1678

1535

1377

Med

Watts

-

1002

978

960

941

914

880

839

798

764

750

Cfm

-

2389

2291

2216

2120

2020

1952

1852

1727

1617

1549

High

Watts

-

-

-

1080

1080

1066

1041

1008

972

938

-

Cfm

-

-

-

2316

2181

2122

2101

2000

1802

1672

-

* Air delivery values are based on operating voltage of 230v or 460v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain

static pressure available for ducting.
NOTES:

1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below

this point.

2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.

20