The ability to properly perform maintenance on this equip-
ment requires certain expertise, mechanical skills, tools, and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment other than those
procedures recommended in the User’s Manual. FAILURE
TO HEED THIS WARNING COULD RESULT IN SERI-
OUS PERSONAL INJURY AND POSSIBLE DAMAGE TO
THIS EQUIPMENT.
Failure to follow these warnings could result in serious
personal injury:
1. Turn off electrical power to the unit and install lockout tag
before performing any maintenance or service on the unit.
2. Use extreme caution when removing panels and parts. As
with any mechanical equipment, personal injury can result
from sharp edges, etc.
3. Never place anything combustible either on, or in contact
with, the unit.
Table 9—Wet Coil Air Delivery (Deduct 10 percent for 208v)*
Horizontal and Downflow Discharge
Unit 50GX024-060
230 AND 460 VOLT
Unit
Motor
Speed
External Static Pressure (in. wg)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
024
Low
Watts
281
282
281
278
276
-
-
-
-
-
-
Cfm
833
776
702
638
554
Med
Watts
-
-
-
375
370
363
357
352
-
-
-
Cfm
-
-
-
894
800
754
636
518
-
-
-
High
Watts
-
-
-
-
-
468
457
444
431
423
-
Cfm
-
-
-
-
-
884
802
697
467
397
-
030
Low
Watts
246
244
243
241
-
-
-
-
-
-
-
Cfm
910
806
749
680
-
-
-
-
-
-
-
Med
Watts
343
339
336
332
328
322
317
-
-
-
-
Cfm
1148
1104
1028
958
850
782
645
-
-
-
-
High
Watts
-
-
-
-
441
432
421
410
400
-
-
Cfm
-
-
-
-
1102
988
896
783
529
-
-
036
Low
Watts
-
470
458
445
430
415
399
384
-
-
-
Cfm
-
1352
1257
1240
1199
1107
1015
924
-
-
-
Med
Watts
-
-
514
501
487
471
455
438
422
-
-
Cfm
-
-
1338
1295
1288
1181
1111
968
813
-
-
High
Watts
-
-
-
646
636
626
614
602
589
-
-
Cfm
-
-
-
1385
1268
1196
1159
1032
948
-
-
042
Low
Watts
-
625
614
605
593
574
549
518
485
454
-
Cfm
-
1540
1510
1473
1396
1348
1288
1192
1124
1037
-
Med
Watts
-
-
-
-
726
695
661
625
591
561
540
Cfm
-
-
-
-
1648
1593
1530
1446
1352
1237
1114
High
Watts
-
-
-
-
-
-
-
790
766
7421
713
Cfm
-
-
-
-
-
-
-
1616
1492
1394
1283
048
Low
Watts
-
588
577
572
566
556
539
517
491
-
-
Cfm
-
1514
1543
1467
1408
1374
1324
1237
1161
-
-
Med
Watts
-
756
738
719
699
676
650
623
596
572
555
Cfm
-
1785
1765
1706
1628
1577
1503
1421
1357
1298
1253
High
Watts
-
-
-
-
896
862
829
800
775
752
728
Cfm
-
-
-
-
1880
1804
1704
1547
1565
1406
1367
060
Low
Watts
903
898
873
842
814
792
777
764
743
701
618
Cfm
2190
2158
2081
2026
1958
1866
1822
1744
1678
1535
1377
Med
Watts
-
1002
978
960
941
914
880
839
798
764
750
Cfm
-
2389
2291
2216
2120
2020
1952
1852
1727
1617
1549
High
Watts
-
-
-
1080
1080
1066
1041
1008
972
938
-
Cfm
-
-
-
2316
2181
2122
2101
2000
1802
1672
-
* Air delivery values are based on operating voltage of 230v or 460v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
20