Installation & User Guide
AX200 Installation & User Guide – July 2007
1 5
Door forced / held open alarm settings can be accessed through Main Screen • Access Point •
(Enable) Door Contact.
For more information about these settings please refer to Access Point Configuration • Access
Point Settings on this manual.
Note: Relay No.3 generates a 1 second pulse through the Access Granted connection block,
located at the top of AX200 board. The connection is normally closed and the pulse is generated
once the access is granted through either door.
Diagrams on the following pages illustrate the connections between the AX200 components.
Please note that if you are installing a brand new unit, the Fire Alarm, Break glass & PSU
Monitoring links will not be activated until the first time they are used.
Break glass Wiring AX200
Breakglass
Door 1
OUT
Breakglass
Door 2
IN
PSU
Monitoring
Volt Free
NC
C
NC
2A
2A
3A
3A
2A
3A
3
to lock
2
AX200
Power In
+12vDC
Double Pole
Breakglass
Breakglass Wiring AX200
Terminal
Function
Terminal
1
Normally Open
1A
2
Common
2A
3
Normally Closed
3A
S
w
it
ch
1
Sw
itc
h
2
AX100
NO
NC
C
L
o
ck R
e
la
y
1
1A
for monitoring of
breakglass