beautypg.com

Carrier 012 User Manual

Page 5

background image

Table 1B — Physical Data (English)

BASE UNIT 50QJ

008

012

NOMINAL CAPACITY (tons)

6.6

8.2

OPERATING WEIGHT (lb)

Unit

840

940

With Economizer

884

984

Roof Curb

223

223

COMPRESSOR

Hermetic

Quantity

2

2

Oil (fluid oz) (each compressor)

55

70

REFRIGERANT TYPE

R-22

Operating Charge (lb-oz)

Circuit 1

8-2

8-14

Circuit 2

7-0

8-10

OUTDOOR FAN

Propeller

Quantity...Diameter (in.)

1...26

1...26

Nominal Cfm

6100

6900

Motor Hp...Rpm

1

3

...960

1

3

...960

OUTDOOR COIL

Enhanced Copper Tubes, Aluminum Fins, Acutrol™ Feed Device

Rows...Fins/in.

2...17

2...17

Total Face Area (sq ft)

20.5

25.0

INDOOR FAN

Centrifugal

Size (in.)

15 x 15

15 x 15

Type Drive

Belt

Belt

Nominal Cfm

2600

3400

Horsepower per NEC*

1.5

2.0

Maximum Continuous Bhp

2.4

2.9

Motor Frame

56

56

Fan Rpm Range

622-882

692-896

Motor Bearing Type

Ball

Ball

Maximum Fan Rpm

1600

1600

Motor Pulley Pitch Diameter

2.4/3.4

3.4/4.4

A/B (in.)

Fan Pulley Pitch Diameter (in.)

5.5

7.0

Belt — Type...Length (in.)

A...48

A...51

Pulley Center Line Distance (in.)

16.75-19.25

18.25-20.75

Fan Shaft Diameter at Pulley (in.)

1

1

Speed Change per Full Turn of

52

42

Movable Pulley Flange (rpm)

Movable Pulley Maximum Full

5

5

Turns from Closed Position

Factory Setting — Full Turns Open

5

5

Factory Speed Setting (Rpm)

620

690

INDOOR COIL

Enhanced Copper Tubes, Aluminum Double Wavy Fins,

Acutrol Feed Device

Rows...Fins/in.

3...15

3...15

Total Face Area (sq ft)

8.0

10.0

OUTDOOR-AIR INLET SCREENS

Cleanable

Quantity...Size (in.)

1...20 x 25 x 1
1...16 x 25 x 1

RETURN-AIR FILTERS

Disposable

Quantity...Size (in.)

4...16 x 20 x 2

4...20 x 20 x 2

LEGEND

Bhp — Brake Horsepower
NEC — National Electrical Code (U.S.A. Standard)
*Used to determine wire sizing per NEC.

5