beautypg.com

Carrier 012 User Manual

Page 11

background image

Table 2 — Electrical Data

UNIT

50LJQ

NOMINAL

V-PH-HZ

VOLTAGE

RANGE

COMPR

(each)

OFM

IFM

ELECTRIC HEAT POWER SUPPLY ELECTRIC HEAT

POWER WIRING

FIG. NO.

ELECTRIC HEAT

PART NO.

50DJ901—

Min

Max RLA

LRA

FLA

Hp FLA

Nominal

kW*

FLA

MCA

MOCP†

008

220-3-50

198

242

15.3

82.0

1.5

1.5

5.8

41.7

50

9.5

24.7

70.3

80

10

711

14.6

38.0

85.7

90

10

601

22.7

59.0

130.0

150

11

611

29.3

76.2

158.5

175

11

621

38.8

100.9

179.5

200

12

711, 621**

400-3-50

360

440

7.7

41.0

1.5

1.5

2.6

10.5

15.2

21.4

25

7

681

12.5

18.0

44.0

45

7

631

21.0

30.3

59.3

60

8

641

25.0

36.1

66.5

70

8

651

31.5

45.5

78.3

80

9

681, 641**

012

220-3-50

198

242

19.6 105.0

1.5

2.0

7.5

53.1

60

9.5

24.7

81.6

90

10

711

14.6

38.0

97.1

100

10

601

29.3

76.2

141.3

150

11

621

43.9

114.1

190.9

200

13

601, 621**

400-3-50

360

440

10.4

55.0

1.5

2.0

3.5

10.5

15.2

28.4

35

7

681

12.5

18.0

51.0

60

7

631

21.0

30.3

66.3

70

8

641

25.0

36.1

73.5

80

8

651

31.5

45.5

85.2

90

9

681, 641**

37.5

54.2

96.6

100

9

631, 651**

LEGEND

COMPR — Compressor
FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor-Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

OFM

Outdoor-Fan Motor

RLA

Rated Load Amps

*Heaters are field-installed only. Heater capacity (kW) is based on

heater voltage of 230 v or 400 v. If power distribution voltage to unit
varies

from

rated

heater

voltage,

heater

kW

will

vary

accordingly.

†Fuse or HACR circuit breaker.

**Requires 2 heater packages.

NOTES:
1. MCA and MOCP values are calculated in accordance with NEC

(National Electric Code) (U.S.A. Standard), Article 440.

2. Motor RLA and FLA values are established in accordance with UL

(Underwriters’ Laboratories) Standard 465 (U.S.A. Standard).

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the % voltage imbalance.
% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 400-3-50.

AB = 393 v
BC = 403 v
AC = 396 v

393 + 403 + 396

Average Voltage =

3

1192

=

= 397

3

Determine maximum deviation from average voltage.
(AB) 397 − 393 = 4 v
(BC) 403 − 397 = 6 v
(AC) 397 − 396 = 1 v
Maximum deviation is 6 v.
Determine % voltage imbalance.

6

% Voltage Imbalance = 100 x

= 1.5%

397

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

11

This manual is related to the following products: