Certified dimension print – Carrier 48SS036 User Manual
Page 6
CERTIFIED DIMENSION PRINT
INDOOR COIL
OUTDOOR COIL
INDOOR COIL ACCESS
REQ’D CLEARANCES FOR SERVICING
— in. (mm)
Duct Panel . . . . . . . . . . . . . . . . . 0
Unit Top . . . . . . . . . . . . . . 36 (914.4)
Side Opposite Ducts . . . . . . . 36 (914.4)
Compressor Access . . . . . . . 36 (914.4)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE
MAT’L — in. (mm)
Maximum Extension of
Overhangs . . . . . . . . . . . 48 (1219.2)
Unit Top . . . . . . . . . . . . . . 14 (355.6)
Duct Side of Unit . . . . . . . . . . 2 (50.8)
Side Opposite Ducts . . . . . . . 14 (355.6)
Bottom of Unit . . . . . . . . . . . . . . . 0
Flue Panel . . . . . . . . . . . . 36 (914.4)
UNIT
48SS
ELECTRICAL
CHARACTERISTICS
UNIT
WEIGHT
CORNER WEIGHT
(lb/kg)
lb
kg
A
B
C
D
048080
208/230-1-60, 208/230-3-60,
460-3-60, 575-3-60
438
199
113/51
89/40
164/75
72/33
048100/120/140
208/230-1-60, 208/230-3-60,
460-3-60, 575-3-60
450
205
116/53
92/42
165/75
77/35
060080
208/230-1-60, 208/230-3-60,
460-3-60, 575-3-60
477
217
123/56
99/45
173/79
82/37
060100/120/140
208/230-1-60, 208/230-3-60,
460-3-60, 575-3-60
489
222
126/57
102/46
173/79
88/40
UNIT
48SS
CENTER OF GRAVITY
(in./mm)
X
Y
Z
048080
28.54/724.9
20.00/508.0
17.66/448
048100/120/140
28.22/716.8
20.05/509.3
17.66/448
060080
28.18/715.8
20.19/512.8
17.66/448
060100/120/140
27.79/705.9
20.23/513.8
17.66/448
NEC (National Electrical Code) REQ’D CLEARANCES — in. (mm)
Between Units, Control Box Side
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 (1066.8)
Unit and Ungrounded Surfaces, Control Box Side . . . . . . . . . . . . . . . . . . . . 36 (914.4)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side . . . . . . . . . . . . . . . . . . . . . . . . . 42 (1066.8)
NOTE: Clearances must be maintained to prevent
recirculation of air from outdoor fan discharge.
6